Mitsubishi P192 Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 144 -
HWE09120 GB
Operation
Outdoor unit model
PUHY-P240TSJMU-A
PUHY-P120TJMU-A PUHY-P120TJMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
21.1°C/ - [70°F/ - ]
Outdoor
8.3°C/6.1°C [47°F/43°F]
Indoor
unit
No. of connected
units
Unit
6
No. of units in opera-
tion 6
Model - 18/36/36/36/48/48
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe 10 [32-3/4 ]
Total pipe length 65 [213-1/4]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz] 25 [55]
Outdoor
unit
Electric current A 59.7
Voltage V 230
Compressor frequency Hz 81 81
LEV open-
ing
Indoor unit
Pulse
373/332/332/332/406/406
SC (LEV1) 0
LEV2 2100 2100
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi] 2.70/0.65 [392/94] 2.70/0.65 [392/94]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
70 [158] 70 [158]
Heat exchanger out-
let (TH3) -1 [30] -1 [30]
Accumulator inlet -1 [30] -1 [30]
Accumulator outlet -1 [30] -1 [30]
Compressor inlet -1 [30] -1 [30]
Compressor shell
bottom 40 [104] 40 [104]
Indoor
unit
LEV inlet 36 [97] 36 [97]
Heat exchanger
inlet 69 [156] 69 [156]