Mitsubishi P192 Air Conditioner User Manual


 
[ IX Troubleshooting ]
- 163 -
HWE09120 GB
1. Error Code
High pressure fault 2 (Outdoor unit)
2. Error definition and error detection method
If the pressure of 0.098MPa [14psi] or lower is registered on the pressure sensor immediately before start-up, it will trigger an
abnormal stop, and error code "1302" will be displayed.
3. Cause, check method and remedy
1. Error Code
Refrigerant overcharge
2. Error definition and error detection method
An error can be detected by the discharge temperature superheat (TdSH).
1) If the formula "TdSH 10°C [18°F]" is satisfied during operation (first detection), the outdoor unit stops, goes into the 3-minute
restart mode, and starts up in three minutes.
2) If a TdSH of 10°C [18°F] or below is detected again (second detection) within 30 minutes of the first stoppage of the outdoor
unit as described above, the outdoor unit stops again, goes into the 3-minute restart mode, and restarts after three minutes.
3) If a TdSH of 10°C [18°F] or below is detected (sixth detection) within 30 minutes of the fifth stoppage of the outdoor unit as
described above, the unit comes to an abnormal stop, and "1500" appears on the display.
4) If a TdSH of 10°C [18°F] or below is detected after 30 minutes have elapsed after a stoppage of the outdoor unit, the unit will
follow the same sequence as the first detection of the condition as described in section 1) above.
5) The period of 30 minutes after a stoppage of the outdoor unit is regarded as a preliminary error, and a preliminary error code
appears on the LED display.
3. Cause, check method and remedy
1302
Cause Check method and remedy
(1) Inner pressure drop due to a leakage. Refer to the page on the troubleshooting of the high
pressure sensor.(page 240)
(2) Pressure sensor failure
(3) Shorted-circuited pressure sensor cable due to torn
outer rubber
(4) A pin on the male connector on the pressure sensor
is missing or contact failure
(5) Disconnected pressure sensor cable
(6) Failure of the pressure sensor input circuit on the
controller board
1500
Cause Check method and remedy
(1) Overcharged refrigerant Refer to the page on refrigerant amount
evaluation.(page 125)
(2) Thermistor input circuit failure on the control board Check the temperature and pressure readings on the sen-
sor that are displayed on the LED monitor.
(3) Faulty mounting of thermistor (TH4) Check the temperature and pressure readings on the
thermistor that are displayed on the LED monitor.
(4) Outdoor unit LEV2a, b actuation failure -> Heating Refer to the section on troubleshooting the LEV.
(page 245)