Mitsubishi Electronics PUZ-A36NHA2 Air Conditioner User Manual


 
45
10-5. TROUBLESHOOTING BY INFERIOR PHENOMENA
Phenomena
Factor Countermeasure
1. Remote controller display does not
work.
2. “PLEASE WAIT” display is remained
on the remote controller.
3. When pressing the remote controller
operation switch the OPERATION
display is appeared but it will be
turned off soon.
1After cancelling to select function from the remote
controller, the remote controller operation switch will
not be accepted for approx. 30 seconds.
1Normal operation
1At longest 2 minutes after the power supply “PLEASE
WAIT” is displayed to start up.
2Communication error between the remote controller
and indoor unit
3Communication error between the indoor and outdoor
unit
4Outdoor unit protection device connector is open.
1DC12V is not supplied to remote controller.
(Power supply display is not indicated on LCD.)
2DC12~15V is supplied to remote controller, however,
no display is indicated.
“PLEASE WAIT” is not displayed.
“PLEASE WAIT” is displayed.
1Check LED2 on indoor controller board.
(1) When LED2 is lit.
Check the remote controller wiring for
breaking or contact failure.
(2) When LED2 is blinking.
Check short circuit of remote controller
wiring.
(3) When LED2 is not lit.
Refer to phenomena No.3 below.
2Check the following.
Failure of remote controller if “PLEASE
WAIT” is not displayed
Refer to phenomena No.2 below if
“PLEASE WAIT” is displayed.
1Normal operation
2Self-diagnosis of remote controller
3”PLEASE WAIT” is displayed for 6 min-
utes at most in case of indoor/outdoor unit
communication error. Check LED3 on
indoor controller board.
(1)When LED3 is not blinking.
Check indoor/outdoor connecting wire
for miswiring.
(Converse wiring of S1 and S2, or
break of S3 wiring.)
(2)When LED3 is blinking.
Indoor/outdoor connecting wire is nor-
mal.
4Check LED display on outdoor controller
circuit board. Refer to 10-10.
Check protection device connector (63L
and 63H) for contact failure.
Refer to 10-9.
Error Code
Abnormal point and detection method
Case Judgment and action
A8
(6608)
M-NET NO RESPONSE
Abnormal if a message was transmitted
and there were reply (ACK) that message
was received, but response command
does not return. Transmitting side detects
abnormality every 30 seconds, 6 times
continuously.
Note) The address and attribute displayed
at remote controller indicate the con-
troller that did not reply (ACK).
1 Transmitting condition is
repeated fault because of
noise and the like.
2 Extension of transmission wire
voltage and signal is caused
by over-range transmission
wire.
• Maximum distance ······200m
[656ft]
Remote controller line
··(12m
[39ft])
3 Extension of transmission wire
voltage and signal is caused
by type-unmatched transmis-
sion wire.
Type ······
With shield wire-
CVVS, CPEVS
With normal wire (no shield)-
VCTF, VCTFK, CVV
CVS, VVR, VVF, VCT
Diameter····1.25mm
2
[AWG16]
or more
4 Accidental malfunction of
abnormality-generated
controller
1 Check transmission waveform or noise on
transmission wire.
2 Turn off the power supply of outdoor unit and
indoor unit and FRESH MASTER or LOSS-
NAY at the same time for 2 minutes or more,
and turn the power on again. If malfunction
was accidental, the unit returns to normal. If
the same abnormality generates again, con-
troller of displayed address and attribute
may be defective.
OCH429--2.qxp 07.11.20 9:18 AM Page 45