4-4 Interlocked Setting
To interlock the operation of LOSSNAY with the run/stop status of the indoor units, click on [Initial
Settings]-[Interlocked LOSSNAY] in the menu to bring up the Interlocked LOSSNAY screen, and enter the
interlock conditions. Click [Save Settings] to send setting data to the GB-24A.
Note: If the user logs in as a manager, the operations may be prohibited.
(1) Click in the Interlocked LOSSNAY registration field to display the
[Select a Unit Address] screen, and click on the numbers
corresponding to the units to be registered. The ones that are
selected will be shown with a yellow-green background. To cancel
the selection, click on them again. Deselected items will be shown
with a gray background.
(2) Click on the Interlocked Indoor Unit Registration field to display
the [Select Unit Addresses] for the indoor units, and click on the
numbers corresponding to the units to be registered. The ones
selected will be highlighted with a yellow-green background. To
cancel the selection, click on them again. Deselected items will be
shown with a gray background.
Note: A maximum of 16 indoor units can be registered to operate with
one ventilator.
Interlocked LOSSNA
Y
Registration
Register the interlocked
ventilation equipment here.
Click to bring up the registration
screen.
Interlocked Indoor Units
Registration
Register the indoor units to
which LOSSNAY units are
interlocked here. Click to bring
up the registration screen.
Refresh
Read setting data from
GB-24A.
Save Settings
Send setting data to GB-24A.