Mitsubishi Electronics GB-24A Air Conditioner User Manual


 
16
(3) To register remote controllers in a group, click on the [Remote
Controller Registration] field to display the [Select Unit Addresses]
screen, and click on the numbers corresponding to the units to be
registered. The ones that are selected will be shown with a
yellow-green background. To cancel the selection, click on them
again. Deselected items will be shown with a gray background.
Note: A maximum of 2 remote controls can be registered in one group.
Note: MA remote controls do not need to be registered to a group.
(4) To register system remote controllers in a group, click on the
[System Controller Registration] field to display the [Select Unit
Addresses] screen, and click on the numbers corresponding to
the units to be registered. The ones that are selected will be
shown with a yellow-green background. To cancel the selection,
click on them again. Deselected items will be shown with a gray
background.
Note: The combined number of system controllers and remote controls cannot
exceed four.
4-3-3 Registering general equipment in the group
(1) To register general equipment in a group, click on the [Air
Conditioner and General Equipment Registration] field to
display the [Select Unit Addresses] screen, and select the
[General Equipment (via PAC-YG66DCA)].
Click the device No. of the general interface device
(PAC-YG66D) that is connected to the general equipment
to be registered. The selected No. will be displayed with a
red frame (selected state), and select the contact No. to
which the general equipment is connected.
To disconnect the general equipment, select the interface
device No., and click the contact No. that has been selected. The No. will be displayed in gray (unselected
state).
Note: A maximum of 16 general equipment can be registered in one group.
Note: To change the registered units to general equipment in the group in which air-conditioners are registered, disconnect the
air-conditioners first.
(2) To change the icon, click the right or left arrow.
(3) In the [Allow Operation] section, select whether to enable or disable the ON/OFF operation on the Web
browser operation screen. Select [In batch and on individual group] to enable only when the collective
operation is performed. Select [On individual group] to enable in each group. Select [No operation (Monitor
only)] to disable.
(4) In the [Monitor] section, select whether to display I/P to or from the general equipment on the monitor
screen.