Mitsubishi Electronics G-50A Air Conditioner User Manual


 
-25-
MENU WED 15:29
1
ADDRESS
SETTING
2
FUNCTION
SELECT
4
GROUP
SETTING
PLEASE
SET
INITIAL
SETTING
3
IP
ADDRESS
SETTING
MENU WED 15:29
6
ADDRESS
SETTING
M-NET ADDRESS
7
FUNCTION
SETTING
BACK
8
IP
ADDRESS SETTING
6
M-NET ADDRESS: 000
5 - 1 Shifting to initial setting menu
5 . Initial setting
5 - 2 M-NET address setting
Function select setting of this controller
Indoor unit address
Set all the M-NET models of indoor units from 001, next, set the address of the K control indoor unit.
Indoor unit address
001 M-NET indoor unit maximum address K control indoor unit mini-
mum address 050
Shift to the initial setting menu by continuously pressing + (2seconds or longer) on the user operation menu
screen.(Refer to section "3-2".)
When group information is not saved, the following initial setting screen is displayed when power is turned on at this
controller.
Shift to the user operation menu by continuously pressing + (2seconds or longer) on the initial setting screen
(Refer to section "3-2".)
(1) Select "6.ADDRESS SETTING"(or "1.ADDRESS SETTING).
(2) Set the controller address by pressing the to switches.(000,201 250).
(3) When the switch is pressed after setting, the screen returns.
When the controller is shipped from the factory, the address is set to "000".
(Always set the address to "000" When the K transmission converter is managed.)
Observe the following precautions when this controller manages the M-NET models and K control mod-
els by using the K transmission converter (PAC-SC25KAA).
Refer to the K transmission converter instruction manual for further details.
Address of this controller
Always set the address of this controller to "000" .
Always set the No.3 function setting to ON.
NOTE :
Press the
Press the switch
to select"6ADDRESS
SETTING"
switch to back
to the initial
setting menu.
* The K transmission converter (PAC-SC25KAA) is not included in systems shipped to North America
(USA & Canada).
1
0
6
9
INS.
BACK
SCREEN
BACK
SCREEN