5 - 1 Shifting to initial setting menu
5 . Initial setting
5 - 2 M-NET address setting
• Function select setting of this controller
• Indoor unit address
Set all the M-NET models of indoor units from 001, next, set the address of the K control indoor unit.
Indoor unit address
001 M-NET indoor unit maximum address K control indoor unit mini-
mum address 050
• Shift to the initial setting menu by continuously pressing + (2seconds or longer) on the user operation menu
screen.(Refer to section "3-2".)
• When group information is not saved, the following initial setting screen is displayed when power is turned on at this
controller.
Shift to the user operation menu by continuously pressing + (2seconds or longer) on the initial setting screen
(Refer to section "3-2".)
(1) Select "6.ADDRESS SETTING"(or "1.ADDRESS SETTING).
(2) Set the controller address by pressing the to switches.(000,201 250).
(3) When the switch is pressed after setting, the screen returns.
• When the controller is shipped from the factory, the address is set to "000".
(Always set the address to "000" When the K transmission converter is managed.)
Observe the following precautions when this controller manages the M-NET models and K control mod-
els by using the K transmission converter (PAC-SC25KAA).
Refer to the K transmission converter instruction manual for further details.
• Address of this controller
Always set the address of this controller to "000" .
Always set the No.3 function setting to ON.
NOTE :
Press the
Press the switch
to select"6ADDRESS
SETTING"
switch to back
to the initial
setting menu.
* The K transmission converter (PAC-SC25KAA) is not included in systems shipped to North America
(USA & Canada).