36
7-2 Night setback control
To use Night setback control (abbreviated to setback control below), click [Functions 3] on the menu, and then
click [Setback Control]. Air conditioning group can be set for this control.
This control prevents indoor dew by heating automatically when the room temperature goes outside of the
specific range during the night.
Note: This control starts heating operation when the control object group stops and the temperature drops below the Min.
temperature. Also this control starts cooling operation when the control object group stops and the temperature rises above
the Max. temperature.
Note: If the room temperature is measured by the air-conditioner's suction temperature sensor, the temperature may not be
correct when the air-conditioner is inactive and the air is not fresh. When the temperature is not measured correctly, switch
the sensor to external temperature sensor (PAC-SE40TSA / PAC-SE41TSA) or remote control sensor.
(1)Select [Use] and set the setback control period.
Note: When [00:00 - 00:00] is set, setback control is active for 24 hours.
(2)Set the control temperature range (Max. and Min.) for each group. For example, suppose [01:00 -
05:00][12°C - --°C] is selected. In this case, heating operation starts automatically when the room
temperature drops below 12°C between 1:00 to 5:00. When the control period is over at 5:00, the set
temperature returns to the original and the operation stops.
Note: During setback operation after the temperature drops below the Min. temperature, when the control period is over or the
room temperature rises to <Min. temperature + 3°C>, the setback control and air conditioning unit stop and the set
temperature returns to the original. In the same way, during setback operation after the temperature rises above the Max.
temperature, when the control period is over or the room temperature drops to < Max. temperature - 3°C>, the setback
control and air conditioning unit stop and the set temperature returns to the original.
Note: When copying settings of a group to another group, click [Copy] button. The screen will change to a selection screen
(yellow-green). Click [Paste] on a group to be copied.
Note: The CITY MULTI model supports a temperature setting range of 12-28°C / 53-83°F when in Heat mode. (When S series
(PUMY) is used, set the temperature at 17°C-28°C / 63-83°F in heat mode.)
(3) Click [Save Settings] to send setting data to AG-150A.
When setback control is active, air conditioning group operates as shown below.
Save settings
Send setting data to AG-150A.
Setback usabilit
y
Select setback usability.
Refresh
Read setting data from AG-150A.
Group number, group
name
Displays group number and
group name.
Control temperature range
Max./Min. temperature for
setback control can be set.
Setback control period
Set the setback control period.
Cool On
24°C
Cool OFF
Cool ON
28°C
24°C
28°C
Cool OFF
24°C
3°C
Setback control period
Max. temperature
When the temperature rises above the Max.
temperature (cooling control)
Setback
operation
starts
Room
temperature
Heat ON
21°C
Heat OFF
Heat ON
12°C
21°C
12°C
Setback
operation
starts
Heat OFF
21°C
Setback control period
Min. temperature
When the temperature drops below the Min.
temperature (heating control)
Room.
temperature
Setback operation stops
(when the temperature
rise 3°C or the control
period is over)