Mitsubishi Electronics AG-150A Air Conditioner User Manual


 
13
4-2-3-2 Settings for when the AG-150A is connected to an existing LAN
When connecting the AG-150A to an existing LAN, consult with the network administrator who is responsible
for the LAN before setting the IP address, subnet mask, or gateway address.
[Example of a Permanent LAN System]
4-2-4 External Input Setting
In the External Input Setting menu, set the AG-150A external input function. By using external input functions,
it is possible to stop and run multiple air conditioners connected to the AG-150A via the separately sold
external I/O adapter for AG-150A (Model: PAC-YG10HA-E) using level signals and pulse signals.
(1) Select [Not in use] when not using the external input function.
(2) Selecting [Emergency stop (Level signal)] makes it possible to stop multiple units by using a level signal.
While this stop operation is being performed, operations such as running or stopping units are prohibited
on the AG-150A unit or remote control.
(3) Selecting [ON/OFF (Level signal)] makes it possible to run or stop multiple units using a level signal. In this mode,
all air conditioner units connected to the AG-150A will be run or stopped and run/stop operations will be
prohibited on the AG-150A unit or remote control.
Web Monitor PC
AG-150A
Backbone LAN
Web Monitor PC
Gateway Gateway
Contact ON
Contact OFF
Normal
Emergency
Stop
Normal
Contact ON
Contact OFF
Stop Run Stop
IP: 10.1.1.250 IP: 10.1.2.250
IP Address :10.1.1.1
Subnet Mask :255.255.255.0
G/W Address :10.1.1.250
IP Address :10.1.1.101
Subnet Mask :255.255.255.0
G/W Address :10.1.1.250
IP Address :10.1.2.51
Subnet Mask :255.255.255.0
G/W Address :10.1.2.250
Receive from the LAN
administrator.
Receive from the LAN
administrator
.
Run/Stop
Connection to AG-150A (CN5)
DC12V
1
2
3
4
5
6
7
8
9
Emergency stop/normal
Connection to AG-150A
(
CN5
)
DC 12V
1
2
3
4
5
6
7
8
9