5-3 Settings for measurement
To measure the temperature or the amount of electricity, click the [Function1]-[Measurement] in the menu, and
open the Measurement screen. Settings for controllers used for measurement can be made.
After the settings are made, click [Save Settings] to send setting data to AG-150A.
Note: To use the measurement data for energy saving (peak cut) control, the energy saving (peak cut) license must be registered.
Check that the license have been registered properly on the license registration screen (refer to chapter8). It is not
necessary to register the license to display the present measurement data or trend graph or to send an error mail.
Note: If the user logs in as a building manager, some of the operations may be prohibited.
5-3-1 Registering AI controllers for temperature/humidity sensors
System settings for measurement sensors can be made. Up to two temperature/humidity sensors can be
connected to one AI controller.
(1) Use the scroll bar, and select the address to which the AI controller (PAC-YG63MCA) is connected.
(2) Select the icon of the AI controller (
) in the column of items to be measured.
Note: To disconnect the AI controller, click the icon of the AI controller that has been selected. The icon will be in unselected state.
(3) Enter the name of the sensor.
(4) Select either the temperature icon (
) or the humidity icon ( ).
(5) Enter the measurable range of the temperature or of the humidity.
Note: When the Pt sensor is connected, the range must be between -30ºC and +60ºC. When the sensors other than the Pt
sensors are connected, enter the ranges that are described in the operation manuals.
(6) To receive an e-mail when the temperature or the humidity exceeds a certain value, set the upper/lower
limit alarm values (occurrence, recovery).
Note: To avoid repeating occurrence and recovery, it is recommended that the difference between the occurrence value and the
recovery value is approx. 1ºC.
Save Settings
Send setting data to AG-150A.
Refresh
Read setting data from AG-150A.
Selection of items to be
measured
Select the items to be measured
between by sensors (such as
temperature/humidity) or by
meters (such as amount o
f
electricity).
Setting details
Set the details for measurement.
Mail sending settings
Set the Type of E-Mail, Mail
Subject, and E-Mail Address.
Selection of separato
r
characte
r
Select the separator characte
r
for CSV file.
Selection of decimal poin
t
characte
r
Select the decimal poin
t
character.
Scroll bar
Switch the address.
Address
Unit address will be displayed
here.
Trend interval
Select the data saving interval.
Address
Items to be
measured
Upper limit
(occurrence)
Upper limit
(recovery)
Upper limit
(recovery)
Lower limit
(occurrence)
Measurable range
Sensor name
Temperature/humidity selection
Settings for upper/lowe
r
limit alarm
Setting Details o
f
sensor 1
Setting Details o
f
sensor 2
Scroll ba
r