5-3-5 Setting the destination to which an error mail is sent
To receive an e-mail when the temperature or the humidity exceeds a certain value, make the error mail
sending settings.
(1) Select [Out-of-limit alarm] in Type of E-Mail pulldown,
and enter the Mail Subject and the E-Mail Address.
Note: The following characters cannot be used in the mail title:
< > & “ ‘
The following format will be applied when the alarm mail is sent.
Item Format
From
AG-150A name + Unit ID
Note: Refer to section 4-2-1 for the settings of the
AG-150A name and unit ID.
Date/Time
yyyy/MM/dd hh:mm:ss
Note: The date format set in chapter 4-2-5 will be
applied.
Address M-NET address of AI controller + sensor No.
Current value
Present temperature or humid (one place of
decimals)
Note: The present value may be [**.*] until the value
measured by sensor becomes stable.
Status
" Exceeded upper limit ", " Recovered from upper
limit ", " Exceeded lower limit ", or " Recovered
from lower limit "
Trend Data
Time + Temperature or humidity (for the last 10
minutes)
(2) Click the [E-Mail Settings] to set the mail server
information.
Note: The setting details are the same as those mentioned in
the chapter 5-1-1 and 5-1-2. Refer to those chapters.
From: Mitsubishi Building(000001)
Date/Time: 23/01/2007 09:38:39
Address: 50-1
Current value: 24.9 deg C
Status: Exceeded lower limit
Trend Data:
09:38 25.2 deg C
09:37 25.4 deg C
09:36 25.6 deg C
09:35 25.8 deg C
09:34 26.1 deg C
09:33 26.4 deg C
09:32 26.7 deg C
09:31 27.0 deg C
09:30 27.5 deg C
09:29 27.7 deg C