Lochinvar 1 Boiler User Manual


 
3
Handling ceramic fiber materials
REMOVAL OF COMBUSTION CHAMBER LINING
The combustion chamber insulation in this appliance contains ceramic fiber material. Ceramic fibers can
be converted to cristobalite in very high temperature applications. The International Agency for Research
on Cancer (IARC) has concluded, “Crystalline silica in the form of quartz or cristobalite from occupational
sources is carcinogenic to humans (Group 1).” Normal operating temperatures in this appliance are below
the level to convert ceramic fibers to cristobalite. Abnormal operating conditions would have to be created
to convert the ceramic fibers in this appliance to cristobalite.
The ceramic fiber material used in this appliance is an irritant; when handling or replacing the ceramic
materials it is advisable that the installer follow these safety guidelines.
Avoid breathing dust and contact with skin and eyes.
Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA
requirements for cristobalite at the time this document was written. Other types of respirators may
be needed depending on the job site conditions. Current NIOSH recommendations can be found on
the NIOSH website at http://www.cdc.gov/niosh/homepage.html. NIOSH approved respirators,
manufacturers, and phone numbers are also listed on this website.
• Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
Apply enough water to the combustion chamber lining to prevent airborne dust.
Remove the combustion chamber lining from the appliance and place it in a plastic bag for disposal.
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer
thoroughly.
NIOSH stated First Aid.
Eye: Irrigate immediately.
Breathing: Fresh air.
ƽ WARNING
When servicing boiler –
• To avoid electric shock, disconnect electrical supply
before performing maintenance.
• To avoid severe burns, allow boiler to cool before
performing maintenance.
Boiler operation –
• Do not block flow of combustion or ventilation air to
the boiler.
• Should overheating occur or gas supply fail to shut
off, do not turn off or disconnect electrical supply to
circulator. Instead, shut off the gas supply at a
location external to the appliance.
• Do not use this boiler if any part has been under
water. The possible damage to a flooded appliance
can be extensive and present numerous safety
hazards. Any appliance that has been under water
must be replaced.
Boiler water –
Thoroughly flush the system (without boiler
connected) to remove sediment. The high-efficiency
heat exchanger can be damaged by build-up or
corrosion due to sediment.
Do not use petroleum-based cleaning or sealing
compounds in the boiler system. Gaskets and seals in
the system may be damaged. This can result in
substantial property damage.
Do not use “homemade cures” or “boiler patent
medicines”. Serious damage to the boiler, personnel,
and/or property may result.
Continual fresh make-up water will reduce boiler
life. Mineral buildup in the heat exchanger reduces
heat transfer, overheats the stainless steel heat
exchanger, and causes failure. Addition of oxygen
carried in by makeup water can cause internal
corrosion. Leaks in boiler piping must be repaired at
once to prevent the introduction of makeup water.
Freeze protection fluids –
NEVER use automotive antifreeze. Use only
inhibited propylene glycol solutions which are
specifically formulated for hydronic systems.
Ethylene glycol is toxic and can attack gaskets and
seals used in hydronic systems.
Service Manual