Lenox Elite Series XP14 Units HEAT PUMPS Heat Pump User Manual


 
Page 17
XP14 SERIES
Leak Test Line Set and Indoor Coil
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
TO VAPOR
SERVICE VALVE
(ANGLE OR BALL
TYPE)
HFC−410A
MANIFOLD GAUGE SET
OUTDOOR UNIT
HIGHLOW
NITROGEN
A Connect an HFC−410A manifold gauge set high pressure hose to the
vapor valve service port.
NOTE Ċ Normally, the high pressure hose is connected to the liquid
line port. However, connecting it to the vapor port better protects the
manifold gauge set from high pressure damage.
B With both manifold valves closed, connect the cylinder of HFC−410A
refrigerant to the center port of the manifold gauge set.
NOTE Ċ Later in the procedure, the
HFC−410A container will be replaced by
the nitrogen container.
CONNECT GAUGE SET
A
B
Figure 13. Manifold Gauge Set Connections for Leak Testing
TEST FOR LEAKS
After the line set has been connected to the indoor and
outdoor units, check the line set connections and indoor
unit for leaks. Use the following procedure to test for leaks:
1. With both manifold valves closed, connect the cylinder
of HFC−410A refrigerant to the center port of the
manifold gauge set. Open the valve on the HFC−410A
cylinder (vapor only).
2. Open the high pressure side of the manifold to allow
HFC−410A into the line set and indoor unit. Weigh in
a trace amount of HFC−410A. [A trace amount is a
maximum of two ounces (57 g) refrigerant or three
pounds (31 kPa) pressure]. Close the valve on the
HFC−410A cylinder and the valve on the high pressure
side of the manifold gauge set. Disconnect the
HFC−410A cylinder.
3. Connect a cylinder of dry nitrogen with a pressure
regulating valve to the center port of the manifold
gauge set.
4. Adjust dry nitrogen pressure to 150 psig (1034 kPa).
Open the valve on the high side of the manifold gauge
set in order to pressurize the line set and the indoor unit.
5. After a few minutes, open one of the service valve
ports and verify that the refrigerant added to the
system earlier is measurable with a leak detector.
6. After leak testing disconnect gauges from service
ports.