Honeywell T7350 Thermostat User Manual


 
T7350 Commercial Programmable Thermostat
63-2605—06
32
APPENDIX - PDA USAGE
See Table 20 for the advanced setup options available through
a PDA.
NOTE: Upon initial thermostat power-up, wait at least 30 sec-
onds before connecting the TIM.
Hardware Requirements
The Thermostat Configuration Tool has the following
configuration:
PDA hardware platform supporting application software.
Serial Connection Cable with TIM. The interface plug
connects to the thermostat socket.
CAUTION
Equipment Damage Hazard
Can damage the TIM connection beyond repair.
Disconnect the TIM cable prior to opening or closing
the thermostat cover.
Setting Clock
It is best to set the clock before downloading anything else to
the thermostat. Connect to the thermostat and set the clock.
See Fig. 26.
NOTES:
When setting the clock the first time, the PDA
displays an incorrect T7350 Clock time, day, and
date.
Day-of-Week mode forces the T7350 to ignore hol-
idays.
Fig. 26. Set Clock menu.
PDA Programming
The PDA Configuration Tool can perform a variety of tasks:
Configure the thermostat.
Calibrate the thermostat.
Perform diagnostics.
NOTE: To install the configuration tool on a second PDA:
1. Power up both PDAs.
2. Execute the following command sequence from
the source PDA: Menu, Beam, T7350, Beam.
Configuration
Whether the configuration is performed offline or while
connected, the procedure is the same.
OFFLINE CONFIGURATION
While disconnected from the thermostat, you can arrange and
save named configurations.
NOTE: The user can note the Configuration ID and manually
set the code using the T7350 user interface.
CONNECT AND CONFIGURE
Connect to a thermostat and:
configure device with existing named parameter
arrangement,
configure device by changing all parameters
read the existing configuration parameter values and
change one or more configuration parameters
save new configuration file.
NOTE: The configuration tool verifies that the subbase
supports the existing arrangement.
CONFIGURATION PROCEDURE
1. Enter the T7350 PDA application. (See Fig. 27.)
2. If disconnected, the only usable functions are:
a. New Config:
(1) Enter a name for the configuration.
(2) Tap New Config.
(3) Proceed to Select Existing Config(uration)
section.
b. Select Existing Config: See below.
Fig. 27. PDA configuration tool main menu.
Select Existing Config(uration)
This function is used to select a programmed configuration
when setting up/programming a T7350. This can be useful
when you use any given configuration more than once.
NOTES:
You can modify details of a given configuration
prior to downloading it into any particular T7350.
The PDA tool will notify you when a selected
configuration requires more stages/features than
the T7350 into which you are downloading it.
Configuration screens will vary depending on the
T7350 model selected.
To configure a T7350:
1. From the opening screen, tap Select Existing Config.
(See Fig. 28.)
2. Select the desired configuration.