Honeywell Ademco Vista Series Commercial Burglary Partitioned Security System With Scheduling Home Security System User Manual


 
10
Partition-Specific Fields
(Duplicate this page for each partition in the installation.)
To program these fields,
1. Press *91 to select a partition.
2. Enter a partition-specific field number (ex. *09).
3. Make the required entry.
4. Repeat steps 1-3 for each partition in the system.
PARTITION #____ PROGRAM FIELDS
1st Page Fields
*09 ENTRY DELAY #1 [02] |
00, 02-15 times 15 seconds.
Maximum 03 for UL Listed installations.
*10 EXIT DELAY #1 [03] |
00, 03-15 times 15 seconds.
Maximum 04 for UL Listed installations.
*11 ENTRY DELAY #2 [06] |
00, 02-15 times 15 seconds.
Maximum 03 for UL installations.
*12 EXIT DELAY #2 [08] |
00, 03-15 times 15 seconds.
Maximum 04 for UL installations.
*13 ALARM SOUNDER DURATION [04] |
01-15 times 2 minutes.
Must be minimum 16 minutes for UL installations.
*16 CONFIRMATION OF ARMING DING [0]
1=enable; 0=disable.
Must be "1" for UL installations.
*22 KEYPAD PANIC ENABLES [001]
1=enable; 0=disable 995 996 999
*23 MULTIPLE ALARMS [1]
1=yes; 0=no.
Must be 1 for UL installations.
*29 QUICK ARM [1]
1=yes; 0=no
*32 PRIM. SUBS. ACCT # | | | |
Enter 00-09; B-F (11-15) [15 15 15 15]
*38 PREVENT ZONE XX BYPASS [00] |
01-86; 000 if all zones (except fire zones) can be bypassed
*39 ENABLE OPEN/CLOSE REPORT [0]
FOR INSTALLER CODE
1=enable; 0=disable
*84 SWINGER SUPPRESSION [01] |
01-15 alarms;
Must be "00" (disabled) for UL installations..
*85 ENABLE DIALER REPORTS FOR PANICS & DURESS
1=enable; [0=disable]
995
996
999
Duress
*87 ENTRY WARNING [1]
1=continuous; 0=3 beeps
*88 BURG. ALARM COMM. DELAY [0]
1=16 seconds; 0=no delay.
Must be "0" for UL installations. Must be 1 for SIA
installations.
*90 SEC. SUBS. ACCT # | | | |
Enter 00-09; B-F (11-15) [15 15 15 15]
2nd Page Programming Fields (press *94)
1*18 AFFECTS LOBBY [0]
Enter 1 if this partition affects the common lobby; enter 0 if it
does not.
1*19
ARMS LOBBY [0]
Enter 1 if arming this partition attempts to arm lobby; enter 0
if it does not
1*20
EXIT ERROR LOGIC ENABLE [0]
0=No; 1=Bypass E/E and Interior zones faulted after exit
delay.
Must be "0" for UL installations.
1*21
EXIT DELAY RESET [0]
0=No; 1=Resets Exit Delay to programmed value after zone
is closed and then faulted prior to end of exit delay.
Must be "0" for UL installations.
1*43 PERM. KEYPAD BACKLIGHT [0]
1=enable; 0=disable. When disabled, display lights when
any key is pressed, and turns off after period of keypad
inactivity.
1*45 EXIT DELAY SOUNDING [0]
1=enable; 0=disable. Produces quick beeping during exit
delay if enabled.
1*47 CHIME ON EXTERNAL SIREN [0]
1=enable; 0=disable
1*52 SEND CANCEL IF ALARM + OFF [1]
1=no restriction; 0=within Bell Timeout period only
1*76 ACCESS CONTROL RELAY FOR PART.[00] |
Relay will be pulsed for 2 seconds whenever code + [0] is
pressed. Enter 00-16; 00=none.
Must be "00" for UL installations.