The Chimney
This unit must be installed into a chimney approved
for use with solid-fuel appliances. In the U.S., it must
be connected to (1) a prefabricated chimney comply-
ing with the requirements for Type HT chimneys in
the Standard for Chimneys, Factory-Built, Residential
Type and Building Heating Appliances, UL 103, or (2)
a code-approved masonry chimney with a ue liner.
In Canada, this unit is listed for use with prefabricat-
ed chimneys tested and listed to the high temperature
(650 degrees C) chimney standard, ULC S-629, or
with a code approved masonry chimney.
The minimum recommended height for any chimney
is 16 ft (4.8 m) above ue collar height. A round ue
(either masonry or approved prefabricated), of either
6" (150 mm), 7" (180 mm) or 8" (200 mm) may be
used. For square or rectangular masonry chimneys,
nominal sizes of 8" x 8" or 8"x 12" (200mm x 200 mm,
200 mm x 300 mm) may be used.
Codes require that solid-fuel chimneys extend 3
ft (0.9 m) above the highest point at which they exit
from the roof. Then, the chimney must extend 2 ft.(6
m) above the highest point within a 10 ft (3 m) radius.
Thus, the 3 foot, 2 foot, 10 foot rule:
3ft. - Above roof exit point
2ft. - Higher than anything within-
10ft. of the chimney.


AN APPROVED CANADIAN
WALL PASS-THROUGH
Hole with a minimum
clearance of 18" (450 mm)
between connector and wall.
Non-combustible cover, one
side only. If two covers are
used, each must be mounted
on non-combustible spacers
at least 7/8" (21mm) away
from the wall.
1" (25mm)
Clearance
AN APPROVED U.S.
WALL PASS-THROUGH
Closest
Combustible
Material
Minimum 2" (50mm)
Clearance to Brick
Minimum 12"
(300mm) to Brick
Liner
Fire Clay
Thimble
Chimney
Connector
Chimney Flue
Masonry Chimney Built to
NFPA 211 Specications.
Minimum 12" (300mm)
to Combustibles
More Than 10 ft. (3m)
10 ft. (3m)
Ridge
Chimney
2 ft. (0.6m) min.
Height Necessary
Above Any Roof Sur-
face Within 10ft. (3m)
3ft. (0.9m)
minimum
above
exit
point
The 3-foot, 2-foot, 10 foot rule


Venting