Hampton Direct H35-NG1 Indoor Fireplace User Manual


 
18 Hampton
®
H35 Direct Vent Freestanding Gas Stove
Review the following sequence of instructions
which are typical of most installations. The se-
quence may vary depending on wall thickness.
See "Exterior Vent Terminal Locations" to
"Venting Arrangements" section for vent
location and clearance dimensions, and the
"Vent Restrictor Position" section to set the
Vent Restrictor to the correct position.
1) Set the unit in its desired location. Check
to determine if wall studs will be in the way
of the venting system, adjust location until
all clearances are met and there are no
obstructions.
Note: A 1-1/2"(38mm) clearance around the
outer pipe must be maintained except
that only a 1" (25mm) clearance is
needed at the termination end.
IMPORTANT:
Do not locate termination hood
where excessive snow or ice
buildup may occur. Be sure to check
vent termination area after snow
falls, and clear to prevent accidental
blockage of venting system. When
using snow blowers, make sure
snow is not directed towards vent
termination area.
b) Install wall thimbles on both interior
and exterior wall with 4 wood screws
(#8 x 1") per thimble.
c) Attach the 2 piece adjustable pipe sec-
tion to the vent terminal and slide into
position from the exterior. The larger
diameter end of the adjustable pipe
goes to the vent terminal.
d) Install the 90
o
elbow onto the adjust-
able pipe to determine the vertical
centerline.
Note: if the centerline cannot be met,
the adjustable sections will have to
be cut.
e) Cut the 4 ft. section of rigid pipe to
length. Attach the 45
o
elbow to the rigid
pipe, and ensure that the pipe length
when cut (with the 45
o
elbow) will seat
onto both the starter collar and the 90
o
elbow. Crimped section of rigid pipe
seats into the 90
o
elbow. Only cut
the uncrimped side of pipe.
Dismantle all pipe sections including vent
terminal.
2) Assemble a trial fi t to determine the vertical
center-line for the vent termination.
a) Cut a 9-1/2" x 9-1/2" (241mm x 241
mm) square hole on both the interior
and exterior wall.
INSTALLATION
DV STOVE HORIZONTAL VENT KIT
DV 2 ft. Stove Vent Kit (Part # 946-116) and DV 4 ft. Stove Vent Kit (Part #946-216) includes all the parts
needed to install the H35 Direct Vent unit with minimum horizontal and vertical vent dimensions.
For installations that require longer vertical and/or horizontal vents use the Dura-Vent system as
shown in the "Dura-Vent Termination Kit" and "Dura-Vent Venting Components" sections.
Qty. Description
1) 1 Rigid Pipe Section (Kit # 946-116: 2 ft. (1.2m) length,
Kit # 946-216: 4 ft. (1.2m) length), 6-1/2" (165mm)
inside diameter
2) 1 Flex Liner, compressed aluminium 2 ply liner, 4" (102mm)
inside diameter
3) 4 Spring Spacers
4) 1 90 deg. Elbow
5) 1 Adjustable pipe section 13-1/2" to 24" (343mm x 610mm), 2 pcs.
6) 1 Thimble Cover
7) 1 Wall Thimble (2 pcs.)
8) 1 Adapter
9) 1 AstroCap Termination Cap
10) 2 Trim Collars
11) 1 Tube of Mill-Pac, high temperature sealant
12) 12 Screws, #8 x 1/2" Self tapping, Stainless Steel
13) 14 Screws, #8 x 1/2" Self tapping, Black
14) 4 Screws #8 x 1-1/2" Drill Point, Black
15) 4 Screws #8 x 1-1/2" Drill Point, Stainless Steel
16) 8 Wood screws #8 x 1"
Required but not included in above Kit:
45
o
Elbow (Part #: 946-214)
Note:
a) Liner sections should be con-
tinuous without any joints or
seams.
b) This is an approved system,
therefore components in this
system must not be substituted
for any other manufacturer's
products.
DV STOVE HORIZONTAL VENT KIT (#946-116 & #946-216) INSTALLATION