Goodman Mfg CVM96 Gas Heater User Manual


 
36
After 2 minutes, the IFC increases to 57% at a rate
of 1% per second
After 10 total minutes, the IFC increases to 78% at a
rate of 1% per second.
After 20 total minutes, the IFC increases to 100% at
a rate of 1% per second for the remainder of the call
for heat.
The circulator is adjusted to the appropriate CFM,
corresponding to the current firing rate.
MIN.
50%
60%
(80%)
70%
IGNITION
10 MINS.
8 MINS.
2 MINS.
Operation with Conventional 2-Stage Thermostat
(DIP switch selects 2-stage heat)
Call for 1st-Stage Heat - Thermostat contacts close R to W1.
After a successful Light Off Sequence and expiration of the
Ignition Stabilization Period:
The IFC adjusts to the low firing rate.
After 2 minutes, the IFC increases to 50% fort he
next 8 minutes.
Thereafter, the IFC will increase 10%, at a rate of 1%
per second, every 10 minutes for the remainder of
the call for heat (See above figure).
The circulator is adjusted to the appropriate CFM,
corresponding to the current firing rate.
MIN.
50%
60%
(80%)
70%
IGNITION
10 MINS.
8 MINS.
2 MINS.
90%
Operation with Conventional 2-Stage Thermostat
(DIP switch selects 2-stage heat)
Call for 2nd-Stage Heat - Thermostat contacts close R to W1
and W2.
After a successful Light Off Sequence and expiration of the
Ignition Stabilization Period:
The IFC adjusts to the low firing rate.
After 2 minutes, the IFC increases to 80%.
Thereafter, the IFC will increase 10%, at a rate of 1%
per second, every 10 minutes for the remainder of
the call for heat.
The circulator is adjusted to the appropriate CFM,
corresponding to the current firing rate.
MIN.
50%
78%
(80%)
100%
IGNITION
2 MINS.
CALL FOR
2ND STAGE HEAT
UNIT CALL FOR HEAT ENDS
Call for 2nd-Stage Heat with 1st-Stage call for heat call in
progress, with conventional 2-Stage Thermostat.
The IFC increases the firing rate to 100% at a rate of
1% per second for the remainder of the W2 call.
The circulator is adjusted to the appropriate CFM,
corresponding to the current firing rate.
Call for 2nd-Stage Heat satisfied; Call for 1st-Stage Heat re-
mains.
The IFC remains at the current firing rate until the
1st-Stage call for heat is satisfied.
HEATING O PERATION WITH CTK01AA THERMOSTAT
(COMMUNICATING)
When the Thermostat Heat Setup DIP switch is set
to 2-Stage heat, the IFC operation will be compatible
with a CTK01AA communicating thermostat.
When a call for heat is sent, the furnace will go through
the Light Off Sequence, at which time the Heat Current
Demand Status will still show 0%. After the successful
Light Off Sequence and expiration of the Ignition
Stabilization Period:
The IFC adjusts to the low firing rate.
After 2 minutes, the IFC accepts the specific Heat
Requested Demand.