FMI MM33 Indoor Fireplace User Manual


 
www.fmiproducts.com
125160-01A 19
WEIGHT DETERMINATION
The following are dead load weight estimates for the Grand Meridian Fireplace.
Table I
Fireplace Model MM33 MM39 MM44 MM49 MM63
Fireplace Weight 835 lbs. 1,194 lbs. 1,250 lbs. 1,359 lbs. 1,704 lbs.
Mortar, Rebar & Ready Mix
Concrete
200 lbs. 350 lbs. 357 lbs. 364 lbs. 370 lbs.
Firebrick Lining 290 lbs. 333 lbs. 345 lbs. 356 lbs. 435 lbs.
Damper/Anchor Plate 17 lbs. 17 lbs. 17 lbs. 17 lbs. 21 lbs.
Steel Platform 89 lbs. 94 lbs. 96 lbs. 100 lbs. 132 lbs.
Floor Area
37" x 28"
(7.2 ft²)
42" x 28"
(8.12 ft²)
48" x 28"
(9.33 ft²)
53" x 28"
(10.30 ft²)
67" x 28"
(13 ft²)
Other Weight Considerations:
1) Fireplace nished facing (surround): This information needs to be obtained from the contractor.
2) Weight of metal ue or Masonry Chimney System: See chimney manufacturer’s weight specications.
Some chimney systems can weigh up to 50 lbs per lineal foot.
Table II - Deection Limits
Construction L S or W D +L
1
Floor Members I/360 --- I/240
1
For wood structural members having a moisture content of less than 16 per cent at time of installation and used under
dry conditions, the deection resulting from L + 0.5D is permitted to be substituted for the deection resulting from
L + D.
Note that FMI PRODUCTS, LLC cannot accept responsibility for structural oor support details. All drawings are
presented as mere illustrations to indicate the presence of the underlying oor system. It is the responsibility of the
general contractor/installer to consult with a local licensed design professional for guidance in building a proper oor
support system.
SUPPORTING FLOOR SYSTEMS INSTALLATION
Continued
Figure 27 - Floor Joist Installation Figure 28 - Floor Joist Installation
I-JOISTS
Anchor
Brackets
I-Joist
Anchoring
Bottom
View
Example Only
I-Joist
Simpson
Strong-Tie
A-35 or
equivalent
I-Joist Anchoring
Top View
Example Only