Enviro 1200 Fireplace Freestanding Stove User Manual


 
33
Figure 35: Freestanding Installation into existing replace.
Unless you are experienced, we recommend
installation by your dealer or a professional
installer.
Many venting manufacturers have listed kits
available to connect a stove to a masonry replace.
Always follow the vent manufacturer’s installation
instructions.
The existing damper may have to be
removed to allow installation.
Installation
MASONRY FIREPLACE INSTALLATION - FREESTANDING:
MOBILE HOME INSTALLATION:
SPECIAL REQUIREMENTS: Pedestal models 1200 and 1700 are approved for mobile homes. A 1200
or 1700 Insert may also be installed into a Mobile Home in the U.S. provided there is a Mobile Home
approved Factory Built Fireplace installed with adequate fresh air supply, and that that Factory Built
Fireplace is not altered beyond the damper or ash shelf being modied. In Canada, Insert Mobile Home
installations must be pre-approved by the local inspector. All freestanding installation requirements in
Installation Of A Listed, Factory Built Chimne
y”, must comply with all local codes that may apply, and
the following must be met:
VENTING:
In Canada: Any ULC-S629 listed chimney system with the accompanying double-wall vent connector.
In U.S.A. Any UL-103-HT listed chimney system with the accompanying double-wall vent connector.
Do not connect a listed chimney of one manufacture with a listed double wall connector from another
manufacture.
Floor Protection
Combustible Floor
Masonry Fireplace
Rain Cap
Steel Plate or Flashing
Rigid Stainless
Steel Liner
Damper Removed
or Fastened Open
Clean-out tee
Chimney
Support and Clamp
Clean-out
cover
Flexible Stainless
Steel Section
Stainless Steel
Connector Pipe
Listed Liner
Stove pipe must
end higher than liner