Emerson 3000 Furnace User Manual


 
Air-Cooled Models—Self-Contained Compressor
24
Figure 14 Air-cooled condensers
Table 4 Air-cooled condenser statistics
Model
Number
of Fans
Connection Sizes
(OD Copper)
Net Weight
lb (kg)
“A” Dimension
in (mm)Hot Gas (in.) Liquid (in.)
083 1 7/8 5/8 295 (133.8) 42 (1067)
104 1 1-1/8 5/8 315 (142.8) 42 (1067)
165 2 1-1/8 7/8 425 (193) 82 (2083)
Secure each leg to condenser frame at all
points shown using hardware provided.
Liquid line
* B
TYPICAL FOOTPRINT
Liebert Lee-Temp heater
pad connection box
*B - Inverted traps are to be field-supplied and installed
(typ). When installing traps, provide clearance for swing
end of access door. Traps are to extend above base of
coil by a minimum of 7-1/2" (190 mm)
Liquid line
Hot gas line
Electric service
supplied by
others
Electric
service
supplied by
others
Hot gas
line
* B
LIEBERT LEE-TEMP CONDENSER
FAN SPEED AND VFD CONDENSER
44"
(1118mm)
18" (457.2mm)
43-9/16"
(1106mm)
51-7/16"
(1306.5mm)
37-7/8"
(962mm)
Common to all models. See Table 4
below for key to “A” dimension.
CONDENSER MOUNTING
1"
(25.4mm)
1-3/4"
(44.5mm)
4-1/4"
(108mm)
4-1/4"
(108mm)
1-3/4"
(44.5mm)
1"
(25.4mm)
1-3/4"
(44.5mm)
1" typ.
(25.4mm)
1-3/4"
(44.5mm)
37-11/16"
(957.3mm)
1-3/4"
(44.5mm)
A
9/16" (14.3mm)
diameter holes
8 places for
1/2" (12.7mm)
diameter bolts
43-3/16"
(1097mm)
SINGLE FAN AIR-COOLED CONDENSERS
1" typ.