DSCover Satellite Products SCW904x Home Security System User Manual


 
Self Contained Wireless Alarm System v1.0
56
Appendix D: SIA False Alarm Reduction
SIA Feature
Programming Section
Comments Range/Default Require-
ment
Exit Time
[005], 3rd entry
Access to Entry and Exit delays and Bell Time Out for the system
Range:
45- 255 seconds
Default:
60 sec.
Required
(programmable)
Progress Annunciation/
Disable - for Silent Exit
[014], Option 6 ON
Enables audible exit beeps from the keypad for the duration of exit delay Keypads may be disabled
Default:
Enabled
Allowed
Exit Time Restart
[014], Option 2 ON
Enables the exit delay restart feature
Default:
Enabled Required
Auto Stay Arm on
Unvacated Premises
[001]-[002] Zone type 05, 06
Function Key: Stay Arming. All Stay/Away type zones (05, 06) will be automatically
bypassed
If no exit after full arm
Default:
Enabled
Required
Exit Time and Progress
Annunciation/Disable
or Remote Arming
[005] and [014] bit 6
System Times and Audible Exit beeps can be disabled when using the Key fob to arm
away the system
Default:
Enabled Allowed
Entry delay(s)
[005], 1st and 2nd entry
Access to Entry and Exit delays and Bell Time Out for the system
Note:
Combined Entry delay and Communications Delay (Abort Window) shall not
exceed 60s
Range:
30 sec. to 4 min.
Default:
30 sees
Required
(programmable)
Abort Window
for Non-Fire zones
[101]-[134] bit 6 ON
Access to zone attributes, i.e, swinger shutdown, transmission delay and cross zone.
Individual zones attribute bit 6 (Transmission delay) is by default ON
May be disabled
by zone or zone type
Default:
Enabled
Required
Abort Window - for
Non-Fire zones
[377], 4th entry
Access to the programmable delay before communicating alarms
Note:
Combined Entry delay and Communications Delay (Abort Window) shall not
exceed 60s
Range:
15 - 45 sec.
Default:
30 sees
Required
(programmable)
Abort Annunciation
[382], Option 3 ON
Enables the “Communication Cancelled” message display on keypad Annunciate that no
alarm was transmitted
Default:
Enabled
Required
Cancel Annunciation
[328], 8th entry
Access to the reporting code for Alarm Cancelled Annunciate that a
Cancel was transmitted
Default:
Enabled
Required
Duress Feature
[*][5] Master Code
Option 2 ON
Do not derive code from an existing Master/User code (e.g., Master code is 1234, the
duress code should not be 1233 or 1235)
No 1+/- derivative of another
user code. No duplicates with
other user codes
Default:
disabled
Allowed
Cross Zoning
[016] Option 1
[101]-[134] bit 8 OFF
This option enables Cross Zoning for entire system. Individual zones can be enabled
for Cross zoning via Zone attribute bit 8 in sections [101] - [134]
Programming required
Default:
Disabled
Required
Cross Zone Timer
[176]
Access to the programmable Cross Zone timer May program
Range: 001-255 sec./min.
Default:
60 secs
Allowed
Swinger Shutdown for Alarms
[377] 1st entry
Access to the swinger shutdown limit for zone alarms For all non-fire zones
shut down at 1 or 2 trips
Default:
1 Trip
Required
(programmable)
Swinger Shutdown Enable
[101] - [134] bit 6 ON
Access to zone attributes, i.e., swinger shutdown, transmission delay and cross zone.
Individual zones attribute bit 6 (Swinger shutdown enabled) is by default ON
For non-police
response zones
Default:
Enabled
Allowed
24-Hr. Auto_verified Fire
(Wireless) Zone type [89]
Access to 24-Hr. Auto_verified Fire (Wireless) Activates If a restoral is Not
received within the specified
time
Default:
disabled
Required
Call Waiting Cancel Dial String
[304], [382], Option 4 OFF
Access to the dialing sequence used to disable call waiting Dependant on user phone
line
Default:
disabled
Required
Testing
System Test:
[*][6] Master Code, Option 4
The system activates all keypad sounders, bells or sirens for 2 seconds and all keypad lights turn on.
Refer to the User Manual (part no. 29007326).
Walk Test Mode:
[*][6] Opt 8
This mode is used to test each zone on the system for proper functionality.
Alarm Communications
During Walk Test
[382] Option 2:
Enables Communication of zone alarms while Walk Test is active.
Walk Test End and Begin
Reporting Codes
[348], 1
st
and 2
nd
Entries
Access to the reporting codes for Walk Test Begin and Walk Test End.
WWW.DIYALARMFORUM.COM