DSCover Satellite Products SCW904x Home Security System User Manual


 
Self Contained Wireless Alarm System v1.0
34
Section [005] System Times
After entering Section [005], program the Entry Delay 1, Entry Delay 2 and Exit Delay for the system. Entries are in seconds. Program the Bell
Cut-Off Time. Valid entries are in minutes.
Section [006] Installer Code
The default Installer Code is [5555] or [555555] if 6-Digit Access Codes is enabled.
Section [007] Master Code
The default Master Code is [1234] or [123456] if 6-digit Access Codes is enabled.
Section [009] I/O Programming (Zones/PGMs)
The alarm system has two on-board terminals that are programmable as hardwired zones (Zones 33 and 34) or low current PGMs (PGM1 and
PGM2). Enter the 2-digit zone definition or 2-digit PGM option required based on I/O type selected in Section [013] Opt [1] & [2].
PGM Output Options:
Section [012] Keypad Lockout
The system can be programmed to ‘lockout’ the keypad if a series of incorrect user or installer codes are entered. When lockout is active, the sys-
tem will emit a steady 2-second error tone when a key is pressed. Program the Number of Invalid Codes Before Lockout with the desired number.
Valid entries are from [000] to [255]. Program data [000] to disable the feature. The keypad will remain locked out for the number of minutes pro-
grammed for the Lockout Duration. Valid entries are from [000] to [255].
[37]
Night Zone: Functions like Interior Stay/Away (05) but will remain bypassed if the user presses [
][1] to re-activate Stay/Away
zones when armed in the Stay mode
[87] Delayed 24-Hour Fire (Wireless): Instant audible alarm when violated, communication delayed 30 seconds. If the alarm is
acknowledged during the time delay (by pressing a key), the alarm will be silenced for 90 seconds and then the cycle is repeated.
If the alarm is not acknowledged the alarm will latch and communicate after the 30 second delay.
[88] Standard 24-Hour Fire (Wireless): Instant Alarm and Communication when violated.
[89] Auto-verified 24-Hour Fire (Wireless): When the detector begins to sound, the system will monitor for a restoral transmission.
If a restoral is not received within 40 seconds, the system will go into alarm and communicate with the central station. If a
restoral is received within the 40 second period and a second detector of this zone type begins to sound within 80 seconds of the
restoral, the system will also go into alarm and communicate with the central station.
Option Description
[00] Null PGM: Not Used
[01] Residential Fire and Burglary: Output will activate (steady for burglary, pulsing for fire) if an alarm occurs.
[02]-[04] Future Use
[05] System Armed Status: Output will activate when the system is armed
[06] Ready to Arm: Output will activate when system is in the Ready state (Ready light ON)
[07] Keypad Buzzer Follows Output: Activates when the keypad buzzer is activated for 24 hour Supervisory, Zone Alarms, Entry
Delay, Audible Exit Delay, No Activity Arming Pre-alert, Audible Exit Fault and Door Chime.
[08] Courtesy Pulse: Output will activate during entry/exit delay when the system is armed – will remain active for an additional 2
minutes after the entry or exit delay expires
[09] System Trouble Output (with trouble options): Output will activate when any selected trouble condition is present.
[10] System Event Output (with trouble options): Output will activate when any selected condition occurs. Output can be
programmed to follow timer.
[11] System Tamper: Output will activate when any tamper condition is present (i.e., zones)
[12] TLM and Alarm: Output will activate if a telephone line trouble is present and then an alarm occurs
[13]-[16] Future Use
[17] Away Armed Status: Activates when the system is armed in Away mode
[18] Stay Armed Status: Activates when system is armed in Stay mode
[19] Command Output 1:Activates when a [][7][1] command is entered on the keypad – Command can be programmed to require a
valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
[20] Command Output 2: Activates when a [][7][2] command is entered on the keypad – Command can be programmed to require
a valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
WWW.DIYALARMFORUM.COM