Desa (V)T32N SERIES Indoor Fireplace User Manual


 
www.desatech.com
111986-01D 35
TROUbLESHOOTING
Continued

 
 
 

 -

 

Fireplace produces unwanted
odors
Gas odor even when control knob
is in OFF position
Gas odor during combustion
Dark residue on logs or inside of
replace

1. Gas leak.  

1. Gas leak.  

2. Control valve defective
1. Gas leak.  

1. Improper log placement
2. Air holes at burner inlet
blocked
3. Burner ame holes blocked
4. Improper venting or excessive
blockage
5. Excessive amounts of embers
and pan material
REMEDY
1. Locate and correct all leaks
(see Checking Gas Connec-
tions, page 21)
1. Locate and correct all leaks
(see Checking Gas Connec-
tions, page 21)
2. Replace control valve
1. Locate and correct all leaks
(see Checking Gas Connec-
tions, page 21)
1. Properly locate logs (see In-
stalling Logs, Lava Rock, and
Glowing Embers, page 25)
2. Clean out air holes at burner
inlets. Periodically repeat as
needed
3. Remove blockage
4. Have the vent system inspect-
ed, including the termination
cap. Remove any restrictions
or obstruction
5. Clear excess embers until a
minimum gap of 1/2" remains
under the grate