Desa (V)T32N SERIES Indoor Fireplace User Manual


 
www.desatech.com
111986-01D6
PRE-INSTALLATION
PREPARATION
Continued
Figure 4 - Framing Clearances for
Installation Against an Exterior Wall
Figure 5 - Framing Clearances for Corner
Installation
C
B
A
D
E
F
G
Top of Louver
Opening
3
2
1
4
5
6
7
Wall
Ref.
Mantel
Depth Ref.
Mantel from Top of
Louver Opening
1 14" A 16"
2 12" B 14"
3 10" C 12"
4 8" D 10"
5 6" E 8"
6 4" F 6"
7 2" G 4"
Figure 6 - Clearances for Combustible
Mantels
CLEARANCES
Minimum clearances to combustibles for the re-
place are as follows:
*Back and sides 0"
Perpendicular walls 6"
Floor 0"
Ceiling to louver opening 42"
Front 36"
Top of Standoffs 0"
Vent (See venting
instructions for specic
venting clearances.)
Combustible material with a maximum thickness of
5/8" may be ush with the top front of replace.
* For back and sides of replace, do not pack with
insulation or other materials. 0" clearance to com-
bustible materials are for framing purpose only.
    -







    
-



FRAMING AND FINISHING
Figure 4 shows typical framing of this replace.
Figure 5 shows framing for corner installation. All
minimum clearances must be met.
For available accessories for this replace, see
Accessories on page 36. If you are using a sepa-
rate combustible mantel piece, refer to Figure 6
for proper installation height. You can install
noncombustible mantels at any height above the
replace.
Note: Noncombustible mantels may discolor!
32
3
/
8
"
34
5
/
8
"
19"
A
B
E
F
G
H
D
C
Nailing Tabs
28
1
/
2
"
13
5
/
8
"
39
3
/
8
"
9
1
/
2
"
9
7
/
8
"
34
3
/
8
"
34
5
/
8
"
54
1
/
8
"
Nailing
Tabs