Country Flame FP42 Indoor Fireplace User Manual


 
FIREPLACE FURNACE SAFETY LABEL (PP-741)
Version 7.1
ix
Model FP33, FP37, FP42 Solid (Wood) Fuel
W/N 11667 Fireplace/Furnace
Tested to UL 391, UL 127, UL 1482
Listing Report #32048002-E Electrical Rating: 120 V, 6.5 Amps, 60/50 Hertz
INSTALLATION: Use only chimneys suitable for solid fuel. The use of air filters is not required. Place only
on non-combustible flooring with adequate support. Maintain the following clearances to combustibles:
24” = Fireplace Furnace opening to combustible sidewall
24” = Floor level non-combustible hearth extension
8” = Non-combustible hearth extension on each side of opening
12” = Combustible mantle above outlet air grilles
2” = Warm air duct to combustibles
Static pressure = 0.25” wc
CHIMNEY SIZE:
Models FP33 and FP 37 use 13” x 13” masonry flue or 10” listed type HT or UL 103 flues.
Model FP 42 use 13” x 17” masonry flue or 12” listed type HT or UL 103 flues.
Refer to owner's manual supplied with this appliance. Burn Wood Only. Load fuel carefully or damage may
result.
WARNING:
Do not store fuel within the above clearances.
Do not use chemical fluids to start the fire.
Do not burn garbage, gasoline, naphtha, engine oil, or other flammable liquids.
Inspect and clean chimney regularly.
The heat exchanger, flue pipe, and chimney must be cleaned regularly to remove accumulated creosote and ash.
Ensure that the heat exchanger and chimney are cleaned at the end of the heating season to minimize corrosion
during the summer months.
CAUTION – Hot surfaces:
Keep children away.
Do not touch during operation.
DURING AN ELECTRICAL POWER FAILURE, IF FIREPLACE DOORS ARE INSTALLED,
COMBUSTION AIR CONTROL SHOULD BE OPEN TO ONLY THE MINIMUM SETTING WITH
DOORS CLOSED.
In case of a "run-away" fire, be sure all doors are closed tightly and the combustion air control is at the
minimum setting.
DO NOT CONNECT THIS UNIT TO A CHIMNEY SERVING ANOTHER APPLIANCE.
Manufactured by: COUNTRY FLAME TECHNOLOGIES Marshfield, MO 65706
Manufacturer Date: