Carrier R-410A Air Conditioner User Manual


 
5
Table 1A — 40RUA Physical Data, English — Cooling Units
LEGEND
UNIT 40RUA* 25 28 30
NOMINAL CAPACITY (Tons) 20 25 30
OPERATING WEIGHT (lb)
Base Unit with TXV 730 1050 1062
Plenum 225 325 325
FANS
Qty...Diam. (in.) 2...15 2...18 2...18
Nominal Airflow (cfm) 8,000 10,000 12,000
Airflow Range (cfm) 6,000 – 10,000 7,500 – 12,500 9,000 – 15,000
Nominal Motor Hp (Standard Motor)
208/230-3-60 and 460-3-60 5.0 7.5 10.0
575-3-60 5.0 7.5 10.0
Motor Speed (rpm)
208/230-3-60 and 460-3-60 1745 1745 1745
575-3-60 1745 1755 1755
REFRIGERANT R-410A
Operating charge (lb)
(approx per circuit)
3.5 4.5 5.0
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig) 450
Face Area (sq ft) 19.88 24.86 29.83
No. of Splits 222
No. of Circuits per Split 18 20 24
Split Type...Percentage Face...50/50
Fins/in. 17 15 15
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 2...1
1
/
8
2...1
3
/
8
2...1
3
/
8
DX Coil — Liquid Refrigerant (ODF) 2...
5
/
8
Steam Coil, In (MPT) 1...2
1
/
2
Steam Coil, Out (MPT) 1...
1
/
2
Hot Water Coil, In (MPT) 1...2
Hot Water Coil, Out (MPT) 1...2
Condensate (PVC) 1...1
1
/
4
ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size (in.)
4...16 x 20 x 2
4...16 x 24 x 2
4...20 x 24 x 2
4...20 x 25 x 2
Access Location Either Side
STEAM COIL
Max Working Pressure (psig at 260°F)
20
Total Face Area (sq ft) 13.33 15.0 15.0
Rows...Fins/in. 1...10 1...10 1...10
HOT WATER COIL
Max Working Pressure (psig) 150
Total Face Area (sq ft) 13.33 15.0 15.0
Rows...Fins/in. 2...8.5 2...12.5 2...12.5
Water Volume
(gal)
13.9
14.3
(ft
3
) 1.85 1.90
DX Direct Expansion
TXV Thermostatic Expansion Valve
Units are shipped without refrigerant charge.
Field installed accessory only.