Carrier R-410A Air Conditioner User Manual


 
29
Table 9E — Medium-Static Drive Data, 60 Hz — SI
Table 9F — High-Static Drive Data, 60 Hz — SI
UNIT
40RUA*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS830
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
109.2-
134.6
109.2-
134.6
109.2-
134.6
Pulley Factory Setting
Full Turns Open
3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (mm) 239 239 239
Pulley Bore (mm) 36.5 49.2 49.2
Belt No. — Section 1—B 2—B
2—B
Belt Pitch (mm) 1062
(2) 986
(2) 1011
(2) 986
(2) 1011
FAN SPEEDS (r/s)
Factory Setting 14.7 14.7 14.7
Range 13.3-16.4 13.3-16.4 13.3-16.4
Max Allowable Speed (r/s) 20.0 18.3 18.3
Change per
1
/
2
Turn of
Moveable Motor Pulley
Flange
0.255 0.255 0.255
MAX FULL TURNS FROM
CLOSED POSITION
666
SHAFTS CENTER DISTANCE (mm) 232-279 169-240 169-240
Four belts shipped with unit. Use correct set of 2 belts sized according to the pully setting.
UNIT
40RUA*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS*30
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
109.2-
134.6
109.2-
134.6
109.2-
134.6
Pulley Factory Setting
Full Turns Open
3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (mm) 188 203
203
Pulley Bore (mm) 36.5 49.2 49.2
Belt No. — Section 2—B 2—B 2—B
Belt Pitch (mm) 935 935 960
FAN SPEEDS (r/s)
Factory Setting 18.6 17.1 17.1
Range
16.9-
20.0
14.6-
17.9
14.6-
17.9
Max Allowable Speed (r/s) 20.0 18.3 18.3
Change per
1
/
2
Turn of
Moveable Motor Pulley
Flange
0.323 0.278 0.278
MAX FULL TURNS FROM
CLOSED POSITION
666
SHAFTS CENTER DISTANCE (mm) 207-255 169-240 169-240
It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 20 r/s.