Carrier R-410A Air Conditioner User Manual


 
27
Table 9A — Standard Drive Data, 60 Hz — English
Table 9B — Medium-Static Drive Data, 60 Hz — English
UNIT
40RUA*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS*30
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.) 3.7-4.7 4.3-5.3 4.3-5.3
Pulley Factory Setting
Full Turns Open
3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (in.) 9.4 11.0 11.0
Pulley Bore (in.) 1
7
/
16
1
15
/
16
1
15
/
16
Belt No. — Section 2—B 2—B
2—B
Belt Pitch (in.) 41.8
(2) 42.8
(2) 43.8
(2) 42.8
(2) 43.8
FAN SPEEDS (rpm)
Factory Setting 771 752 752
Range 679-863 682-841 674-831
Max Allowable Speed (rpm) 1200 1100 1100
Change per
1
/
2
Turn of
Moveable Motor Pulley
Flange
15.3 13.1 13.1
MAX FULL TURNS FROM
CLOSED POSITION
666
SHAFTS CENTER DISTANCE (in.)
9.12-
10.99
6.67-
9.43
6.67-
9.43
Four belts shipped with unit. Use correct set of 2 belts sized according to the pully setting.
UNIT
40RUA*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS*30
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.) 4.3-5.3 4.3-5.3 4.3-5.3
Pulley Factory Setting
Full Turns Open
3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (in.) 9.4 9.4 9.4
Pulley Bore (in.) 1
7
/
16
1
15
/
16
1
15
/
16
Belt No. — Section 1—B 2—B
2—B
Belt Pitch (in.) 41.8
(2) 38.8
(2) 39.8
(2) 38.8
(2) 39.8
FAN SPEEDS (rpm)
Factory Setting 881 881 881
Range 798-984 798-984 798-984
Max Allowable Speed (rpm) 1200 1100 1100
Change per
1
/
2
Turn of
Moveable Motor Pulley
Flange
15.3 15.3 15.3
MAX FULL TURNS FROM
CLOSED POSITION
666
SHAFTS CENTER DISTANCE (in.)
9.16-
10.99
6.67-
9.43
6.67-
9.43
Four belts shipped with unit. Use correct set of 2 belts sized according to the pully setting.