Carrier 50PSW036-360 Heat Pump User Manual


 
9
Complete C
Complete C Complete C
Complete C
7
7
Fig. 5 — Typical Aquazone™ 50PSW120 Complete C Control Wiring, 3-Phase
Circuit Breaker
High Pressure Switch
Low Pressure Switch
Fuse
F
NOTES:
1. Compressor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer is wired to 380 v lead (VIO) for 380-3-50 operation. For 420 v
operation switch VIO and BRN leads at L1 and insulate VIO lead.
4. FP1 thermistor provides freeze protection for source water. When using anti-
freeze solutions, cut JW3 jumper.
5. Check installation wiring information for controller hookup. Control wiring must
be Class 1 and voltage rating equal to or greater than unit supply voltage.
6. Transformer secondary ground via Complete C board standoff and screws to
control box. (Ground available from top 2 standoffs as shown.)
7. Aquastat is supplied with unit and must be wired in series with the hot leg of
the pump. Aquastat is rated for voltages up to 277 v.
L-WTR Load Water
NEC National Electrical Code
P1 Field Wiring Terminal Block
RVS Reversing Valve Solenoid
S-WTR Source Water
TRANS Transformer
Factory Line Voltage Wiring
Factory Low Voltage Wiring
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
AL Alarm Relay Contacts
ASTAT Aquastat Device
COMP Compressor
CC Compressor Contactor
DTS Discharge Temperature Switch
FP1 Sensor, Source Low Temp Protection
FP2 Sensor, Load Low Temp Protection
HP High Pressure Switch
HPWS High Pressure Water Switch
HWG Hot Water Generator
JW1 Jumper Wire for Alarm
LOC Loss of Charge Pressure Switch
Relay/Contactor Coil
Solenoid Coil
Thermistor
Ground
Indicator Light
G=Green, R=Red
(Comp On) (Alarm Light)