Carrier 50PSW036-360 Heat Pump User Manual


 
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500073-01 Printed in U.S.A. Form 50PSW-C1SI Pg CL-2 10-10 Replaces: New
Copyright 2010 Carrier Corporation
-
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
HEATING AND COOLING CYCLE ANALYSIS
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =
FLOW RATE (L/s) x TEMP. DIFF. (DEG. C) x FLUID FACTOR* =
(kW)
SUPERHEAT = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE
= (DEG C)
SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE
=
(DEG C)
*Use 500 for water, 485 for antifreeze.
DESCRIPTION HEATING COOLING NOTES
Voltage
Compressor Amp
1 Suction Temperature
2 Suction Pressure
2a Saturation Temperature
2b Superheat
3 Discharge Temperature
4 Discharge Pressure
4a Saturation Temperature
4b Subcooling
5 Liquid Line Temperature
6 Source Water In Temperature
7 Source Water Out Temperature Temperature Difference —
8 Source Water In Pressure
9 Source Water Out Pressure
9a Pressure Drop
9b Flow Rate (L/s)
10 Load Water In Temperature
11 Load Water Out Temperature Temperature Difference —
12 Load Water In Pressure
13 Load Water Out Pressure
13a Pressure Drop
13b Flow Rate (gpm)
COMPRESSOR
DISCHARGE
SUCTION
HWG*
EXPANSION
VALVE
FILTER
DRIER
REVERSING
VALVE
HEATING POSITION COOLING POSITION
1
COAX
COAX
5
1210
1311
9
7
8
6
4
3
2
FP2:
HEATING
LIQUID
LINE
5
FP1:
COOLING
LIQUID
LINE
CONDENSER (HTG)
EVAPORATOR (CLG)
CONDENSER (COOLING)
EVAPORATOR (HEATING)
WATER-TO-WATER UNITS
REFRIG FLOW - HEATING REFRIG FLOW - COOLING
Source
Load
LEGEND
*Turn off HWG (hot water generator)
before troubleshooting.
CLG Cooling
HTG Heating
a50-8465