Table 8 (cont) -- Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 48EZ--A24--60
UNIT
HEATING RISE
RANGE
MOTOR
SPEED
WIRE
COLOR
EXTERNAL ST ATIC PRESSURE (in. W.C.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
48EZ(---,N)A60115
30 --- 60
o
F
(17 --- 33
o
C)
Low Blue
CFM 1445 1389 1341 1281 1236 1189 1139 1072 1027
Heating Rise
(
o
F)
60 NA NA NA NA NA NA NA NA
Heating Rise
(
o
C)
33 NA NA NA NA NA NA NA NA
Med---Low Pink
CFM 1678 1635 1602 1558 1513 1474 1438 1404 1349
Heating Rise
(
o
F)
52 53 54 56 57 59 60 NA NA
Heating Rise
(
o
C)
29 30 30 31 32 33 34 NA NA
Medium
2
Red
CFM 1927 1893 1858 1824 1791 1759 1720 1689 1640
Heating Rise
(
o
F)
45 46 47 48 49 49 51 51 53
Heating Rise
(
o
C)
25 26 26 26 27 27 28 29 29
Med---High
1
Orange
CFM 2131 2088 2065 2013 1982 1941 1888 1860 1785
Heating Rise
(
o
F)
41 42 42 43 44 45 46 47 49
Heating Rise
(
o
C)
23 23 23 24 24 25 26 26 27
High Black
CFM 2461 2409 2339 2286 2192 2140 2062 1968 1874
Heating Rise
(
o
F)
35 36 37 38 40 41 42 44 46
Heating Rise
(
o
C)
20 20 21 21 22 23 23 25 26
48EZ(---,N)A60130
35 --- 65
o
F
(19 --- 36
o
C)
Low Blue
CFM 1445 1389 1341 1281 1236 1189 1139 1072 1027
Heating Rise
(
o
F)
NA NA NA NA NA NA NA NA NA
Heating Rise
(
o
C)
NA NA NA NA NA NA NA NA NA
Med---Low Pink
CFM 1678 1635 1602 1558 1513 1474 1438 1404 1349
Heating Rise
(
o
F)
57 59 60 62 64 65 NA NA NA
Heating Rise
(
o
C)
32 33 33 34 35 36 NA NA NA
Medium
2
Red
CFM 1927 1893 1858 1824 1791 1759 1720 1689 1640
Heating Rise
(
o
F)
50 51 52 53 54 55 56 57 59
Heating Rise
(
o
C)
28 28 29 29 30 30 31 32 33
Med---High
1
Orange
CFM 2131 2088 2065 2013 1982 1941 1888 1860 1785
Heating Rise
(
o
F)
45 46 47 48 49 50 51 52 54
Heating Rise
(
o
C)
25 26 26 27 27 28 28 29 30
High Black
CFM 2461 2409 2339 2286 2192 2140 2062 1968 1874
Heating Rise
(
o
F)
39 40 41 42 44 45 47 49 51
Heating Rise
(
o
C)
22 22 23 23 24 25 26 27 29
* Air delivery values arewithout air filter andare for dry coil (See Table 9 --- 48EZ--- A WetCoil Pressure Droptable).
1
Factory---shipped g as heating speed
2
Factory---shippedheat pump speed
NA --- Notallowed for heatingspeed
Note: Deduct field---supplied air filter pressure drop and wet coil pressure drop to obtain external staticpressure available for ducting.
Shadedareas indicate speed/static combinationsthatare not permitted for dehumidificationspeed.
Note: Deduct 10%f or 208 volt operation.