Table 14 — Carrier VFD (Toshiba TOSVERT VF-S9) Program Parameter Values
*These settings differ from the Toshiba defaults and are required for Carrier applications.
Table 15 — Motor Electronic Thermal Protection (tHr) for Toshiba TOSVERT VF-S9 VFD
*IFM Letter refers to the 15th digit (Motor Option) of the unit model number.
PARAMETER GROUP COMMUNICATION NO. DESCRIPTION CARRIER DEFAULT SETTINGS
Basic Parameters
CNOd 0003 Command Mode Selection 0*
FNOd 0004 Frequency Setting Mode Selection 1*
Fr 0008 Forward/Reverse Run Selection 1*
ACC 0009 Acceleration Time 1 10.0 sec
dEC1 0010 Deceleration Time 1 10.0 sec
FH 0011 Maximum Frequency 60.0 Hz*
UL 0012 Upper Limit Frequency 60.0 Hz*
LL 0013 Lower Limit Frequency 10.0 Hz*
Pt 0015 V/f Control Mode Selection 1*
tHr 0041 Motor Electronic Thermal Protection Level 1 See Table 15*
Sr1 0018 Preset-Speed Operation Frequency 1 60.0 Hz*
Extended Parameters
F115 0115 Input Terminal Selection 5 (S2) 14*
F116 0116 Input Terminal Selection 6 (S3) 11*
Frequency Parameters
F201 0201 VIA/II Input Point 1 Setting 20%*
F202 0202 VIA/II Input Point 1 Frequency 0.0 Hz
F203 0203 VIA/II Input Point 2 Setting 100%
F204 0204 VIA/II Input Point 2 Frequency 60.0 Hz*
Operation Mode Parameters
F300 0300 PWM Carrier Frequency 4 KHz*
F301 0301 Auto-Restart Control Selection 3*
F302 0302 Regenerative Power Ride-through Control 1*
F303 0303 Retry Selection (Number of Times) 2*
F360 0360 PI Control 1*
F362 0362 Proportional Gain 0.30
F363 0363 Integral Gain 0.20
MOTOR STD EFFICIENCY HIGH EFFICIENCY
HP kW IFM Letter* 230V Setting 380V Setting 460V Setting IFM Letter* 230V Setting 460V Setting
53.73 A837783L9083
7.5 5.60 B808884M8084
10 7.46 C857586N8588
15 11.19 D819879P8179
20 14.92 E94— 87Q8887
CC
VIA
VIB
PP
II FM
F
R RST
S1
S2
S3
CC OUT
P24
TWO-WIRE
TRANSDUCER
4-20mA
-
+
FIRE SPEED
OVER-RIDE
E-STOP
LEGEND
Typical Factory Wiring
Optional Field Wiring
Fig. 58 — Toshiba TOSVERT VF-S9 VFD Factory-Installed Jumpers