14
A08060
A08057
Edge Thermidistat Models TP ---PRH ---01 & TP ---NRH ---01
w/ Fan Coil & 2---Stage Air Conditioner
Edge Thermidistat Models TP ---PRH ---01 & TP ---NRH ---01
w/ Furnace & 2---Stage Air Conditioner
RVS/Heat Stage 2 O/W2/B
Heat Stage 1 W/W1
Compressor Low Y1
Compressor High Y/Y2
Fan G
24VAC Hot Heating Rh
24VAC Hot Cooling Rc
Dry Contact 1 D1
Dry Contact 2 D2
24VAC Common C
Humidify HUM
Outdoor Air Temp OAT
Remote Room Sensor RRS
OAT/RRS Return
SRTN
SRTN
Outdoor Sensor
Humidifier Solenoid
Valve
Remote Room
Sensor
O
Y1
W1
G
W2
C
Y2
R
Y1
Y/Y2
R
C
DH
REMOVE J2
JUMPER FOR
HEAT STAGING
REMOVE J1 FOR
DEHUMIDIFY
MODES
Two-Stage
Air Conditione
r
Thermidistat
Variable Speed
Fan Coil
RVS/Heat Stage 2 O/W2/B W2
Heat Stage 1 W/W1 W1
Compressor Low Y1 Y1 Y1
Compressor High Y/Y2 Y/Y2 Y2
Fan G G
24VAC Hot Heating Rh R R
24VAC Hot Cooling Rc
Dry Contact 1 D1
Dry Contact 2 D2 DHUM
24VAC Common C COM C
Humidify HUM
Outdoor Air Temp OAT
Remote Room Sensor RRS
OAT/RRS Return
SRTN
SRTN
Outdoor Sensor
Humidifier Solenoid
Valve
Remote Room
Sensor
THERMIDISTAT
VARIABLE SPEED
FURNACE
TWO-STAGE
AIR CONDITIONER
A09338
Thermidistat Model TP ---PRH ---01 or TP--- NRH ---01
w/ VS Furnace & 2---Stage Air Conditioner
Variable Speed
Furnace
Thermidistat
2-Stage
Air Conditioner
Heat Stage 2 O/B W2 W2
Heat Stage 1 W/W1 W1
Cool Stage 1 Y1 / W2 Y1
Cool Stage 2 Y/Y2 Y/Y2 Y/Y2
Fan G G
24VAC Hot Heating Rh R R
24VAC Hot Cooling Rc
Dry Contact 1 D1
Dry Contact 2 D2 DHUM
24VAC Common C COM C
Humidify HUM
Outdoor Air Temp OAT
Remote Room Sensor RRS
OAT/RRS Com SRTN
Outdoor Sensor *
Humidifier Solenoid
Valve *
Remote Room
Sensor *
* Indicates connection may not be required / available.
LEGEND
24 VOLT FACTORY WIRING
24 VOLT FIELD WIRING
FIELD SPLICE CONNECTION
RELAY SPDT, PILOT DUTY
24-V COIL (HN61KK324)
OR EQUIVALENT
HUMIDISTAT, OPENS ON
HUMIDITY RISE (HL38MG026)
AIRFLOW SELECTOR
R1
H
AFS
A02005
Fig. 10 -- Thermidistat Wiring with 2--Stage Puron refrigerant Air Conditioner
24ANA