81
SECTION XIV: REPAIR PARTS
All V8 Series Boiler Repair Parts may be obtained through your local Burnham Wholesale distributor. Should you require as-
sistance in locating a Burnham Distributor in your area, or have questions regarding the availability of Burnham products or repair
parts, please contact Burnham Customer Service at (717) 481-8400 or Fax (717) 481-8408.
b. Air leaking into oil line causing fl ame out.
c. Defective nozzle causing fl ame to be erratic.
d. Excessive airfl ow or draft causing fl ame to leave
burner head.
e. Excessive back pressure causing fl ame to be
erratic.
3. Control locks out after Trial For Ignition (TFI).
a. No oil to burner.
b. Shorted electrodes.
c. Nozzle clogged.
d. Airfl ow too high.
e. Ignitor module defective.
f. CAD cell defective.
g. Oil valve stuck open or closed.
Note: The Safety Monitoring Circuit (SMC) is
designed to provide lockout in the event of a
stuck or welded motor relay.
ECITON
51nihtiwdehsilbatsetonsiemalffI
nwonk(noitautcaevlavliofosdnoces
lliwtuokcol)]IFT[noitingIroFlairTsa
der
aybdetacidnisituokcoL.rucco
yramirplioehtnodetacolno-dilosDEL
.lortnoc
-skcollortnocehtfiruccolliwpu-hctaL
rofllacagnirudsemit)3(eerhttuo
dnaderybdetacidnisisihT.taeh
.no-diloss'DELrebma