New Buck Corporation 384 Indoor Fireplace User Manual


 
SECTION IX
VENTILATION AIR
VENTILATION AIR FROM INSIDE BUILDING
This fresh air would come from an adjoining unconfined space. When venting to an adjoining space,
you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the
floor on the wall connecting the two spaces. (See Options 1 and 2 below.) You can also remove door
into adjoining room. (See Option 3 below.)
WARNING
REWORK WORKSHEET, ADDING THE SPACE OF THE ADJOINING UNCONFINED
SPACE. THE COMBINED SPACES MUST HAVE ENOUGH FRESH AIR TO SUPPLY ALL
APPLIANCES IN BOTH SPACES.
NOTE: Each opening shall have a minimum free area of 1 square inch per 1000 BTU’s per hour of
the total input ratings of all gas utilization equipment in the confined space, but not less than 100
square inches.
Ventilation Air From Inside Building
Page 33