Bryant 581A/B Heating System User Manual


 
166
ELECTRICAL DATA
LEGEND
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR
breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the following formula to determine the per-
cent voltage imbalance.
% Voltage Imbalance
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance.
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
UNIT
579F
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM IFM
POWER
EXHAUST
COMBUSTION
FAN MOTOR
POWER
SUPPLY
No. 1 No. 2
Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA FLA LRA FLA MCA MOCP*
180
(15 Tons)
208/230 187 253 28.8 195 28.8 195 3 0.5 1.7 3.7 10.5/11.0
0.57 81/81 100/100
4.6 18.8 0.57 85/86 110/110
460 414 508 14.7 95 14.7 95 3 0.5 0.8 3.7 4.8
0.30 40 50
2.3 6.0 0.30 43 50
575 518 633 10.8 80 10.8 80 3 0.5 0.8 3.0 3.9
0.57 30 40
2.1 4.8 0.57 32 40
216
(18 Tons)
208/230 187 253 30.1 225 28.8 195 3 0.5 1.7 5.0 15.8/15.8
0.57 87/87 110/110
4.6 18.8 0.57 92/92 110/110
460 414 508 15.5 114 14.7 95 3 0.5 0.8 5.0 7.9
0.30 44 50
2.3 6.0 0.30 47 60
575 518 633 12.1 80 10.8 80 3 0.5 0.8 5.0 6.0
0.57 34 40
2.1 4.8 0.57 36 40
240
(20 Tons)
208/230 187 253 37.8 239 30.1 225 2 1 6.6 7.5 25.0/25.0
0.57 116/116 150/150
4.6 18.8 0.57 120/120 150/150
460 414 508 17.2 125 15.5 114 2 1 3.3 7.5 13.0
0.30 57 70
2.3 6.0 0.30 59 70
575 518 633 12.4 80 12.1 80 2 1 3.4 7.5 10.0
0.57 44 50
2.1 4.8 0.57 46 50
300
(25 Tons)
208/230 187 253 41.0 350 37.8 239 2 1 6.6 10.0 28.0/28.0
0.57 130/130 150/150
4.6 18.8 0.57 135/135 175/175
460 414 508 21.8 158 17.2 125 2 1 3.3 10.0 14.6
0.30 66 80
2.3 6.0 0.30 68 80
575 518 633 17.3 125 12.4 80 2 1 3.4 10.0 13.0
0.57 54 70
2.1 4.8 0.57 56 70
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
IFM Indoor (Evaporator) Fan Motor
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
NEC National Electrical Code
OFM Outdoor (Condenser) Fan Motor
RLA Rated Load Amps
= 100 x
max voltage deviation from average voltage
average voltage
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
452 + 464 + 455
3
=
1371
3
= 457
% Voltage Imbalance = 100 x
7
457
= 1.53%
0TFQ004-012
579F180-300