100
PERFORMANCE DATA (cont)
COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
Where: h
ewb
= Enthalpy of air entering evaporator coil.
3. The SHC is based on 80 F edb temperature of air entering evapo-
rator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
581B102 (8
1
/
2
TONS) — SUBCOOLING MODE
Temp (F)
Air Ent
Condenser
(Edb)
Air Entering Evaporator — Cfm/BF
2550/0.08 3000/0.09 3400/0.11 4250/0.13
Air Entering Evaporator — Ewb (F)
72 67 62 72 67 62 72 67 62 72 67 62
75
TC 114.1 104.1 97.8 116.3 108.5 103.4 117.6 111.9 108.0 122.2 118.9 111.4
SHC 49.8 64.2 81.2 52.6 70.8 89.0 55.4 76.9 95.4 62.0 87.0 107.2
kW 5.57 5.46 5.44 5.59 5.50 5.44 5.60 5.51 5.44 5.62 5.62 5.69
85
TC 107.3 98.4 92.6 111.0 101.8 98.0 113.0 104.2 102.0 117.1 111.4 106.1
SHC 42.2 58.3 76.0 47.1 64.5 83.5 51.2 70.2 89.2 57.3 81.2 101.2
kW 6.32 6.30 6.15 6.32 6.27 6.18 6.34 6.22 6.20 6.30 6.31 6.45
95
TC 101.9 92.4 86.8 105.3 95.5 92.8 107.4 97.7 96.5 112.1 103.7 100.3
SHC 35.4 51.9 70.3 40.1 58.5 77.9 44.9 64.9 83.7 52.1 74.0 94.8
kW 7.06 7.13 6.93 7.06 7.06 6.95 7.06 6.99 6.98 7.01 7.04 7.17
105
TC 94.5 85.4 77.0 97.6 88.3 82.4 99.9 90.6 88.0 104.1 96.1 94.0
SHC 29.7 45.7 63.2 33.9 52.2 70.1 38.0 58.3 75.7 44.4 67.6 88.5
kW 7.99 8.00 7.81 8.01 7.97 7.85 8.02 7.94 7.89 7.96 7.96 8.08
115
TC 86.4 75.0 68.3 89.3 80.2 74.1 91.4 83.2 78.4 96.5 88.4 87.1
SHC 24.0 38.7 56.4 27.4 45.6 62.9 31.1 51.9 67.0 37.0 60.8 81.8
kW 8.91 8.83 8.66 8.93 8.86 8.76 8.97 8.86 8.84 8.91 8.93 8.90
125
TC 78.6 65.5 60.2 81.3 68.9 64.7 83.3 71.6 68.2 88.5 78.8 78.9
SHC 18.3 32.0 48.8 21.2 38.0 53.5 24.1 44.1 57.5 29.4 53.3 73.8
kW 9.81 9.65 9.53 9.86 9.68 9.64 9.89 9.71 9.75 9.90 9.72 9.88
581B102 (8
1
/
2
TONS) — HOT GAS REHEAT MODE
Temp (F)
Air Ent
Condenser
(Edb)
Air Entering Evaporator — Ewb (F)
75 Dry Bulb
62.5 Wet Bulb
(50% Relative)
75 Dry Bulb
64 Wet Bulb
(55% Relative)
75 Dry Bulb
65.3 Wet Bulb
(60% Relative)
Air Entering Evaporator — Cfm
2550 3000 3400 4250 2550 3000 3400 4250 2550 3000 3400 4250
80
TC 43.44 46.26 48.45 52.38 45.26 48.15 50.39 54.43 46.84 49.79 52.08 56.20
SHC 12.34 16.78 20.29 26.74 5.79 10.15 13.60 19.93 0.11 4.40 7.80 14.03
kW 6.31 6.31 6.31 6.31 6.05 6.05 6.05 6.05 5.83 5.83 5.83 5.83
75
TC 44.33 47.00 49.06 52.78 46.12 48.85 50.97 54.78 47.67 50.46 52.63 56.52
SHC 12.92 17.12 20.44 26.54 6.81 10.94 14.20 20.20 1.51 5.58 8.79 14.70
kW 6.38 6.38 6.8 6.38 6.15 6.15 6.15 6.15 5.95 5.95 5.95 5.95
70
TC 45.22 47.73 49.68 53.18 46.98 49.55 51.55 55.14 48.51 51.14 53.18 56.84
SHC 13.50 17.47 20.59 26.34 7.83 11.73 14.81 20.46 2.92 6.76 9.79 15.36
kW 6.46 6.46 6.46 6.46 6.25 6.25 6.25 6.25 6.07 6.07 6.07 6.07
60
TC 46.99 49.19 50.90 53.97 48.70 50.96 52.71 55.86 50.18 52.49 54.27 57.49
SHC 14.67 18.15 20.90 25.95 9.88 13.31 16.01 20.99 5.73 9.11 11.78 16.68
kW 6.60 6.60 6.60 6.60 6.45 6.45 6.45 6.45 6.32 6.32 6.32 6.32
50
TC 48.77 50.66 52.13 54.77 50.42 52.36 53.87 56.57 51.85 53.83 55.37 58.14
SHC 15.83 18.83 21.20 25.56 11.93 14.89 17.22 21.51 8.55 11.47 13.77 18.01
kW 6.74 6.74 6.74 6.74 6.64 6.64 6.64 6.64 6.56 6.56 6.56 6.56
40
TC 50.54 52.13 53.35 55.56 52.14 53.76 55.02 57.29 53.53 55.18 56.47 58.78
SHC 17.00 19.52 21.51 25.16 13.98 16.47 18.43 22.04 11.36 13.82 15.76 19.33
kW 6.88 6.88 6.88 6.88 6.84 6.84 6.84 6.84 6.81 6.81 6.81 6.81
BF — Bypass Factor
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
t
ldb
=t
edb
–
sensible capacity (Btuh)
1.10 x cfm
t
lwb
= Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h
lwb
)
h
lwb
=h
ewb
–
total capacity (Btuh)
4.5 x cfm
581B036-150