Bryant 580J Air Conditioner User Manual


 
8
Table 2 AHRI COOLING RATING TABLE
Unit
Cooling
Stages
Nom.
Capacity
(tons)
Net Cooling
Capacity (MBH)
Total Power
(KW)
SEER EER IEER
A04 1 3 34.6 3.1 13.0 11.00 N/A
A05 1 4 45.0 4.0 13.0 11.00 N/A
A06 1 5 59.0 5.5 13.0 10.75 N/A
A07 1 6 70.0 6.4 N/A 11.00 11.2
A08 1 7.5 88.0 8.0 N/A 11.00 11.2
D08 2 7.5 83.0 7.5 N/A 11.00 11.7
A09 1 8.5 97.0 8.8 N/A 11.00 11.2
D09 2 8.5 99.0 9.0 N/A 11.00 11.7
A12 1 10 117.0 10.6 N/A 11.00 11.2
D12 2 10 114.0 10.3 N/A 11.10 11.8
D14 2 12.5 140.0 12.9 N/A 10.80 11.0
D16 2 15 174.0 16.1 N/A 10.80 11.7
LEGEND
AHRI --- Air Conditioning, Heating and Refrigeration
Institute Test Standard
ASHRAE --- American Society of Heating, Refrigerating
and Air Conditioning, Inc.
EER --- Energy Efficiency Ratio
IEER --- Integrated Energy Efficiency Ratio
SEER --- Seasonal Energy Efficiency Ratio
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
NOTES:
1. Rated in accordance with AHRI Standard 210/240 or
340/360, as appropriate.
2. Ratings are based on:
Cooling Standard: 80_F(27_C) db, 67_F(19_C) wb
indoor air temp and 95_F(35_C) db outdoor air temp.
IEER Standard: A measure that expresses cooling
part---load EER efficiency for c ommercial unitary air
conditioning and heat pump equipment on the basis of
weighted operation at various load capacities.
3. All 580J units comply with ASHRAE 90.1 Energy
Standard for minimum SEER and EER requirements.
4. 580J units comply with US Energy Policy Act (2005).
To evaluate code compliance requirements, refer to
state and local codes or visit the following website:
http://bcap---energy.org.
580J