22
CURBS & WEIGHTS DIMENSIONS -- 580J 08--12 (cont.)
C101218
Fig. 6 -- 580J 08-- 12
C
B
A
D
C08337
Fig. 7 -- Service Clearance
LOC DIMENSION CONDITION
A
48---in (1219 mm) Unit disconnect is mounted on panel
36---in (914 mm) If dimension --- B is 12 --- in (305 mm)
18---in (457 mm) No disconnect, convenience outlet option
18---in (457 mm) Recommended service clearance (use electric screwdriver)
12---in (305 mm) Minimum clearance (use manual ratchet screwdriver)
B
36---in (914 mm) Unit has economizer
12---in (305 mm) If dimension --- A is 36 --- in (914 mm)
Special Check for sources of flue products within 10---ft of unit fresh air intake h ood
C
36---in (914 mm) Side condensate drain is used
18---in (457 mm) Minimum clearance
D
48---in (1219 mm) No flue discharge accessory installed, surface is combustible material
42---in (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
36---in (914 mm) Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)
Special Check for adjacent units or building fresh air intakes within 10---ft of this unit’s flue outlet
580J