Bryant 580J Air Conditioner User Manual


 
40
Table 2 0 COOLING CAPACITIES 1--STAGE COOLING 6 TONS
580J07 (6 TONS) --- UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODE
A ir E nte r in g E va po ra tor --- C F M
Temp (F) Air Ent
Condenser (Edb)
80 dry bulb 80 dry bulb 80 dry bulb
72 wet bulb 67 wet bulb 62 wet bulb
2100 2400 2700 2100 2400 2700 2100 2400 2700
75
TC 86.7 89.9 92.8 79.3 82.3 84.9 71.9 74.6 77.0
SHC 40.1 41.8 43.3 46.9 48.5 49.9 53.7 55.2 56.5
kW 4.3 4.3 4.3 4.2 4.2 4.2 4.2 4.2 4.2
85
TC 79.5 82.6 85.4 72.5 75.3 77.9 65.4 68.0 70.3
SHC 32.1 34.0 35.7 40.7 42.5 44.1 49.4 51.0 52.5
kW 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.9 4.9
95
TC 72.4 75.3 78.1 65.6 68.3 70.8 58.8 61.3 63.6
SHC 24.1 26.3 28.1 34.6 36.6 38.3 45.1 46.9 48.5
kW 5.8 5.8 5.8 5.7 5.7 5.7 5.6 5.6 5.6
105
TC 65.2 68.1 70.7 58.7 61.4 63.8 52.3 54.7 56.8
SHC 16.2 18.5 20.5 28.5 30.6 32.6 40.7 42.8 44.6
kW 6.5 6.5 6.5 6.4 6.4 6.4 6.3 6.3 6.3
115
TC 58.0 60.8 63.3 51.9 54.4 56.7 45.7 48.0 50.1
SHC 8.2 10.7 13.0 22.3 24.7 26.8 36.4 38.6 40.6
kW 7.2 7.2 7.2 7.1 7.1 7.1 7.0 7.0 7.0
580J07 (6 TONS) --- UNIT WITH PERFECT HUMIDITY SYSTEM IN HOT GAS REHEAT MODE
A ir E nte r in g E va po ra tor --- C F M
Temp (F) Air Ent
Condenser (Edb)
75 dry bulb 75 dry bulb 75 dry bulb
62.5 wet bulb (50% relative) 64 wet bulb (55% relative) 65.3 wet bulb (60% relative)
2100 2400 2700 2100 2400 2700 1750 2000 2700
80
TC 16.7 19.8 22.5 18.8 21.9 24.7 16.2 19.4 26.7
SHC 0.6 0.6 0.6 --- 0.4 --- 0.4 --- 0.4 --- 1.3 --- 1.3 --- 1.3
kW 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
75
TC 17.7 20.6 23.1 19.6 22.6 25.3 17.3 20.3 27.1
SHC 0.6 0.6 0.6 --- 0.3 --- 0.3 --- 0.3 --- 1.2 --- 1.2 --- 1.2
kW 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
70
TC 18.6 21.3 23.7 20.5 23.3 25.8 18.3 21.1 27.6
SHC 0.7 0.7 0.7 --- 0.2 --- 0.2 --- 0.2 --- 1.0 --- 1.0 --- 1.0
kW 4.0 4.0 4.0 4.1 4.1 4.1 4.1 4.1 4.1
60
TC 20.5 22.9 25.0 22.2 24.7 26.8 20.4 22.8 28.5
SHC 0.7 0.7 0.7 --- 0.0 --- 0.0 --- 0.0 --- 0.7 --- 0.7 --- 0.7
kW 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
50
TC 22.4 24.4 26.2 24.0 26.0 27.9 22.4 24.5 29.3
SHC 0.8 0.8 0.8 0.1 0.1 0.1 --- 0.4 --- 0.4 --- 0.4
kW 4.1 4.1 4.1 4.1 4.1 4.1 4.2 4.2 4.2
40
TC 24.3 25.9 27.4 25.7 27.4 28.9 24.5 26.3 30.2
SHC 0.8 0.8 0.8 0.3 0.3 0.3 --- 0.1 --- 0.1 --- 0.1
kW 4.1 4.1 4.1 4.2 4.2 4.2 4.2 4.2 4.2
LEGEND
Edb --- En tering Dry --- Bulb
Ewb --- Entering Wet --- Bu lb
kW --- Compressor Motor Power Input
Idb --- L eaving Dry --- Bulb
Iwb --- Leaving Wet --- Bulb
SHC --- Sensible Heat Capacity (1000 Btuh) Gross
TC --- Total Capacity (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
t
ldb
=t
edb
sensible capacity (Btuh)
1.10 x cfm
t
lwb
= Wet---bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h
lwb
)
h
lwb
=h
ewb
total capacity (Btuh)
4.5 x cfm
Where: h
ewb
= Enthalp y of air entering evaporator coil
580J