Bryant 580J Air Conditioner User Manual


 
50
Table 30 COOLING CAPACITIES 2--STAGE COOLING 12.5 TONS
580J*14D
(RTPF & Novation)
AMBIENT TEMPERATURE
85 95 105 115
EAT (db) EAT (db) EAT (db) EAT (db)
75 80 85 75 80 85 75 80 85 75 80 85
3600 Cfm
EAT (wb)
58
TC 127.6 127.6 142.9 121.7 121.7 137.6 115.0 115.0 130 108.3 108.3 122.6
SHC 110.3 126.6 142.9 105.8 121.7 137.6 99.9 115.0 130 94.1 108.3 122.6
62
TC 136.1 136.1 136.1 131.1 131.1 131.1 123.8 123.8 124.5 114.9 114.9 120.3
SHC 96.6 112.8 129.0 94.7 111.2 127.7 91.4 108.0 124.5 87.3 103.8 120.3
67
TC 146.2 146.2 146.2 142.0 142.0 142.0 136.2 136.2 136.2 128.8 128.8 128.8
SHC 78.5 94.4 110.3 76.9 93.1 109.2 74.7 91.0 107.3 71.7 88.1 104.6
72
TC 155.9 155.9 155.9 152.4 152.4 152.4 147.2 147.2 147.2 140.1 140.1 140.1
SHC 60.1 76.6 93.2 58.7 75.2 91.7 56.8 73.3 89.7 54.2 70.6 87.0
76
TC --- 163.0 163 --- 160.0 160 --- 155.1 155.1 --- 148.2 148.2
SHC --- 62.0 81.8 --- 61.1 80.9 --- 59.5 79.3 --- 57.0 76.3
4200 Cfm
EAT (wb)
58
TC 132.2 132.2 149.5 128.2 128.2 144.9 121.9 121.9 137.8 115.0 115.0 130.1
SHC 115.0 132.2 149.5 111.5 128.2 144.9 106.0 121.9 137.8 99.9 115.0 130.1
62
TC 139.6 139.6 139.6 134.7 134.7 138 128.0 128.0 135.6 119.1 119.1 131.2
SHC 102.5 120.8 139 100.8 119.4 138 98.1 116.8 135.6 93.9 112.6 131.2
67
TC 149.5 149.5 149.5 145.4 145.4 145.4 139.6 139.6 139.6 132.1 132.1 132.1
SHC 81.8 99.6 117.4 80.6 98.7 116.8 78.5 96.9 115.2 75.7 94.3 112.8
72
TC 159.0 159.0 159.0 155.5 155.5 155.5 150.3 150.3 150.3 143.1 143.1 143.1
SHC 61.4 79.6 97.8 60.2 78.5 96.8 58.3 76.7 95 55.8 74.2 92.5
76
TC --- 165.7 165.7 --- 162.8 162.8 --- 157.8 157.8 --- 150.8 150.8
SHC --- 64.6 87.7 --- 63.5 86.3 --- 61.5 83.3 --- 58.9 79.9
4800 Cfm
EAT (wb)
58
TC 136.7 136.7 154.5 133.0 133.0 150.3 127.7 127.7 144.3 120.6 120.6 136.4
SHC 118.9 136.7 154.5 115.7 133.0 150.3 111.0 127.7 144.3 104.9 120.6 136.4
62
TC 142.2 142.2 147.8 137.4 137.4 147.1 131.0 131.0 144.7 122.8 122.8 140.3
SHC 107.7 127.8 147.8 106.2 126.7 147.1 103.6 124.2 144.7 99.3 119.8 140.3
67
TC 152.1 152.1 152.1 148.0 148 148 142.2 142.2 142.2 134.6 134.6 134.6
SHC 84.8 104.3 123.7 83.8 103.8 123.7 82.0 102.3 122.6 79.4 99.9 120.4
72
TC 161.3 161.3 161.3 157.8 157.8 157.8 152.5 152.5 152.5 145.4 145.4 145.4
SHC 62.6 82.2 101.9 61.4 81.4 101.3 59.7 79.7 99.8 57.2 77.3 97.5
76
TC --- 167.7 167.7 --- 164.9 164.9 --- 159.9 159.9 --- 152.8 152.8
SHC --- 66.4 91.4 --- 65 89.2 --- 63.1 86.4 --- 60.5 83.1
5400 Cfm
EAT (wb)
58
TC 140.5 140.5 158.8 136.9 136.9 154.7 131.8 131.8 149 125.2 125.2 141.6
SHC 122.2 140.5 158.8 119 136.9 154.7 114.7 131.8 149 108.9 125.2 141.6
62
TC 144.3 144.3 155.7 139.6 139.6 155 133.5 133.5 152.4 125.8 125.8 147.8
SHC 112.2 133.9 155.7 110.9 132.9 155 108.1 130.2 152.4 103.9 125.8 147.8
67
TC 154.2 154.2 154.2 150.0 150.0 150.0 144.2 144.2 144.2 136.7 136.7 136.7
SHC 87.6 108.6 129.6 86.8 108.5 130.1 85.2 107.3 129.4 82.8 105.1 127.4
72
TC 163.1 163.1 163.1 159.7 159.7 159.7 154.3 154.3 154.3 147.1 147.1 147.1
SHC 63.6 84.6 105.6 62.5 83.9 105.4 60.8 82.5 104.2 58.4 80.2 102
76
TC --- 169.3 169.3 --- 166.5 166.5 --- 161.5 161.5 --- 154.2 154.2
SHC --- 67.6 93.7 --- 66.4 91.7 --- 64.5 89.2 --- 61.9 86.1
6000 Cfm
EAT (wb)
58
TC 143.6 143.6 162.3 140.1 140.1 158.3 135.1 135.1 152.7 128.7 128.7 145.5
SHC 124.9 143.6 162.3 121.8 140.1 158.3 117.5 135.1 152.7 111.9 128.7 145.5
62
TC 146.1 146.1 162.4 141.7 141.7 161.5 135.6 135.6 159.2 128.8 128.8 151.2
SHC 116.1 139.3 162.4 114.7 138.1 161.5 112.1 135.6 159.2 106.4 128.8 151.2
67
TC 155.8 155.8 155.8 151.6 151.6 151.6 145.9 145.9 145.9 138.3 138.3 138.3
SHC 90.1 112.6 135 89.6 112.8 136 88.3 112.0 135.8 85.9 110.0 134.1
72
TC 164.5 164.5 164.5 161.2 161.2 161.2 155.8 155.8 155.8 148.5 148.5 148.5
SHC 64.5 86.7 108.9 63.5 86.3 109.1 61.9 85.1 108.2 59.6 82.9 106.3
76
TC --- 170.6 170.6 --- 167.8 167.8 --- 162.8 162.8 --- 155.5 155.5
SHC --- 68.7 95.8 --- 67.5 94.1 --- 65.7 91.8 --- 63.3 88.8
LEGEND:
--- --- Do not operate in this region
Cfm --- Cubic feet per minute (supply air)
EAT(db) --- Entering air temperature (dry bulb)
EAT(wb) --- Entering air temperature (wet bulb)
SHC --- Sensible heat capacity
TC --- Total capacity
580J