Table 1 2 – PHYSICAL DATA (HEATING) 10 -- 15 TONS
580J**12 580J** 14 580J**16
Gas C onnection
#ofGasValves 1 1 1
Nat. gas supply line press (in. w.g.) / (PSIG) 4 --- 13 / 0.18 --- 0.47 4 --- 13 / 0.18 ---
0.47
5 --- 13 / 0.18 ---
0.47
LP supply line press (in. w.g.) / (PSIG) 11 ---13 / 0.40 --- 0.47 11 --- 13 / 0.40 ---
0.47
11 --- 13 / 0.40 ---
0.47
Heat Anticipator setting (Amps)
1st stage 0.14 0.14 0.14
2nd stage 0.14 0.14 0.14
Natural Gas Heat
LOW
#ofstages/#ofburners(total) 2/4 2/4 2/6
Connection Size 3/4” NPT 3/4” NPT 3/4” NPT
Rollout switch opens / closes 195 / 115 195 / 115 225 / 145
Temperature Rise 25 --- 65 25 --- 65 20 --- 55
MED
#ofstages/#ofburners(total) 2/5 2/5 2/8
Connection Size 3/4” NPT 3/4” NPT 3/4” NPT
Rollout switch opens / closes 195 / 115 195 / 115 225 / 145
Temperature Rise 30 --- 65 30 --- 65 25 --- 60
HIGH
#ofstages/#ofburners(total) 2/5 2/5 2/10
Connection Size 3/4” NPT 3/4” NPT 3/4” NPT
Rollout switch opens / closes 195 / 115 195 / 115 225 / 145
Temperature Rise 35 --- 70 35 --- 70 35 --- 65
Liquid Propane Heat
LOW
#ofstages/#ofburners(total) 2/4 2/4 2/6
Connection Size 3/4” NPT 3/4” NPT 3/4” NPT
Rollout switch opens / closes 195 / 115 195 / 115 225 / 145
Temperature Rise 25 --- 65 25 --- 65 20 --- 55
MED
#ofstages/#ofburners(total) 2/5 2/5 2/8
Connection Size 3/4” NPT 3/4” NPT 3/4” NPT
Rollout switch opens / closes 195 / 115 195 / 115 225 / 145
Temperature Rise 30 --- 65 30 --- 65 25 --- 60
HIGH
#ofstages/#ofburners(total) 2/5 2/5 2/10
Connection Size 3/4” NPT 3/4” NPT 3/4” NPT
Rollout switch opens / closes 195 / 115 195 / 115 225 / 145
Temperature Rise 35 --- 70 35 --- 70 35 --- 65
Low NOx Gas Heat
LOW
#ofstages/#ofburners(total) --- ---
Connection Size --- ---
Rollout switch opens / closes --- ---
Temperature Rise --- ---
MED
#ofstages/#ofburners(total) --- ---
Connection Size --- ---
Rollout switch opens / closes --- ---
Temperature Rise --- ---
HIGH
#ofstages/#ofburners(total) --- ---
Connection Size --- ---
Rollout switch opens / closes --- ---
Temperature Rise --- ---
580J