Bradford-White Corp TG-180I-N(X) Water Heater User Manual


 
43
Figure 39. Illustration Showing the Installation of Vertical Terminations for TG-237I Models.
High Altitude Installations
The default setting for the water is 0-2,000 ft (0-610 m) with dip switch numbers 2 and 3 in the OFF
position. If this water heater is installed at a higher altitude, it is necessary to modify the dip switch
settings according to Table .
Table 9. Dip Switch Settings for High Altitude Installations.
0-2000 ft
(0-610 m)
2001-5200 ft
(610-1585 m)
5201-7700 ft
(1585-2347 m)
7701-10200 ft
(2347-3109 m)
Switch No. 2 OFF OFF ON ON
Switch No. 3 OFF ON OFF ON