Bradford-White Corp TG-180I-N(X) Water Heater User Manual


 
31
Condensate
When the total vent system length is greater than 5 ft (1.52 m), condensate will form which could damage
the water heater. For vent lengths greater than 5 ft (1.52 m), the condensate collector and a trap must be
installed.
Recommended Vent/Air Intake Terminal Position
Terminals should be so positioned as to avoid products of combustion entering openings into buildings or
other flues or vents.
Figure 14. Requirements for Vent/Air Intake Terminal Positions.
Table 8. Required Clearances for Venting.
* For clearances not specified in ANSI Z223.1 / NFPA 54 or CGA-B149, please use clearances in accordance with
local installation codes and the requirements of the gas supplier .
** For other than Direct Vent Appliance, 4 ft (1.22 m) below or to side of opening; 1 ft (300 mm) above opening.