Beckett AFII Burner User Manual


 
13
AFII Burner Manual
RECYCLE. If the ame is lost while the burner is
ring, the control shuts down the burner, enters
a 60 second recycle delay, and then repeats the
above ignition sequence. If ame is lost three
times in a row, the control locks out to prevent
cycling with repetitious ame loss due to poor
combustion.
BURNER MOTOR-OFF DELAY. The fuel valve
is closed and the burner motor is kept on for the
selected motor-off delay time before the control
returns the burner to standby.
7.
8.
Figure 9 - Typical Burner Wiring & Burner Sequence of Operation for R7184P Control.
Refer to the appliance manufacturer’s wiring diagram for actual speci cations.
STANDBY. The burner is idle, waiting for a call for
heat. When a call for heat is initiated, there is a 3-
10 second delay while the control performs a safe
start check.
VALVE-ON DELAY. The ignition and motor are
turned on for a 15 second valve-on delay.
TRIAL FOR IGNITION (TFI). The fuel valve is
opened. A ame should be established within the
15 second lockout time.
LOCKOUT. If ame is not sensed by the end of
the TFI, the control shuts down on safety lockout
and must be manually reset. If the control locks out
three times in a row, the control enters restricted
lockout.
IGNITION CARRYOVER. Once ame is
established, the ignition remains on for 10 seconds
to ensure ame stability before turning off. If the
control is wired for intermittent duty ignition, the
ignition unit stays on the entire time the motor is
running.
RUN. The burner runs until the call for heat is
sati ed. The burner is then sent to burner motor off
delay, if applicable, or it is shut down and sent to
standby.
1.
2.
3.
4.
5.
6.
Feature
Interrupted
ignition
Limited reset,
Limited recycle
Valve-on
delay
Burner motor off
delay
Alarm
Contacts
R7184A YES YES
R7184B YES YES YES
R7184P YES YES YES YES Optional
Control System Features
Section: Burner Controls
61351