Bard FLR110D60F Furnace User Manual


 
Manual 2100-422M
Page 19 of 42
BURNER SETUP AND ADJUSTMENT
PROCEDURES
All oil burner installations should be performed by a
qualified installer in accordance with regulations of the
National Fire Protection Standard for Oil-Burning
Equipment, NFPA31 -- latest edition, and in complete
compliance with all local codes and authorities having
jurisdiction. A qualified installer is an individual or
agency who is responsible for the installation and
adjustments of the heating equipment and who is
properly licensed and experienced to install oil-burning
equipment in accordance with all codes and ordinances.
The proper installation and adjustment of any oil burner
requires technical knowledge and the use of combustion
test instruments. The following procedure must be
followed to correctly adjust the burner to match the
specific characteristics of the installation.
Check all oil lines and connections for leaks.
Connect pressure gauge by removing bleed fitting and
screwing in pressure gauge. See Figure 9.
TABLE 4
FURNACE DATA
ledoM
rebmuN
renruB
epyT
ecanruF
epyT
elzzoN
gnitaeH
tupnI
HUTB
gnitaeH
tuptuO
HUTB
eziSepyTerusserPpmuP
F63D580CF
GFAwolfretnuoC
57.0 *
wolloH°07GISP001
000,501 000,78
56.0000,19000,67
55.0000,77000,46
F63D580HF
GFAyoB-iH
57.0 *
wolloH°07GISP001
000,501 000,78
56.0000,19000,67
55.0000,77000,46
F84D011HF
XNyoB-iH
58.0 *
diloS°06GISP051
000,041 000,611
57.0000,911000,99
F06D011HF
XNyoB-iH
58.0 *
diloS°06GISP051
000,041 000,611
57.0000,911000,99
F63D580FLF
GFAyoB-oL
57.0 *
wolloH°07GISP001
000,501 000,78
56.0000,19000,67
55.0000,77000,46
F84D011FLF
XNyoB-oL
58.0 *
diloS°06GISP051
000,041 000,611
57.0000,911000,99
F06D011FLF
XNyoB-oL
58.0 *
diloS°06GISP051
000,041 000,611
57.0000,911000,99
F63D580RLF
GFAyoB-oL
57.0 *
wolloH°07GISP001
000,501 000,78
56.0000,19000,67
55.0000,77000,46
F84D011RLF
GFAyoB-oL
00.1 *
wolloH°07GISP001
000,041 000,611
58.0000,911000,99
F06D011RLF
GFAyoB-oL
00.1 *
wolloH°07GISP001
000,041 000,611
58.0000,911000,99
F06D041RLF
GFAyoB-oL
52.1 *
wolloH°07GISP001
000,571 000,541
01.1000,451000,721
IMPORTANT
Always use combustion test instruments when
making burner adjustments and draft gauge
when setting the barometric damper. It is
virtually impossible to make accurate and
reliable adjustments using the “eyeball” method.
* Factory Installed Nozzle. Also shown are optional approved nozzle size/type.