Venting the Pellet Stove
PELLET VENT MUST MAINTAIN A MINIMUM 3" CLEARANCE TO ANY
COMBUSTIBLE (INSTALL VENT AT CLEARANCES SPECIFIED BY THE
VENT MANUFACTURER).
DO NOT CONNECT THE PELLET VENT TO A VENT SERVING ANY
OTHER APPLIANCE OR STOVE.
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM
OF THIS UNIT.
USE AN APPROVED WALL THIMBLE WHEN PASSING THE VENT
THROUGH WALLS AND A CEILING SUPPORT/FIRE STOP SPACER
WHEN PASSING THE VENT THROUGH CEILINGS (MAKE SURE TO
MAINTAIN 3" CLEARANCE TO ANY COMBUSTIBLES.
No more than 180° of elbows (two 90° elbows, or two 45° & one 90° elbow, etc.).
Maximum Venting
Distance:
Vent must have a
support bracket every
5' of pellet vent when
exterior of structure
If the heater is
installed at an altitude
over 4,000' use 4"
diameter for all
applications
0 Feet
5 Feet
10 Feet
(max.)
0 Feet
5 Feet
10 Feet
15 Feet
20 Feet
25 Feet
30 Feet
33 Feet
(max.)
Use 4 diameter
vent if venting
into this shaded
region.
Use 3 or 4
diameter
vent if
venting into
this shaded
region.
The vent height and run
must not exceed the
distance shown in the
shaded region shown to the
right.
NOTE: To achieve optimum
performance, we
recommend keeping the
vent as short as possible
(horizontal run especially).