51InRoom Precision AC Tech Data Manual
Information common to both modes PACW211
Cabinet Size 1
PACW311
Cabinet Size 2
PACW452
Cabinet Size 3
PACW612
Cabinet Size 4
PACW862
Cabinet Size 5
Connection Sizes
Humidifier Supply Line - mm (in) 6 (1/4) 6 (1/4) 6 (1/4) 6 (1/4) 6 (1/4)
Condensate Drain Line - mm OD (in ID) 21 (3/4) 21 (3/4) 21 (3/4) 21 (3/4) 21 (3/4)
Fan Information
Number of Fans11223
Air Flow - M³/hr (CFM) 7034 (4,140) 10007 (5,890) 14000 (8,240) 19386 (11,390) 24007 (14,130)
External Static Pressure - Pa (in WC) 50 (0.2) 50 (0.2) 50 (0.2) 50 (0.2) 50 (0.2)
Sound Power Level - dBA 76.6 79.7 78.6 83.4 82.7
Total Fan Power Consumption - kW (hp) 2.0 (2.7) 2.3 (3.1) 3.6 (4.8) 6.3 (8.4) 7.3 (9.8)
Humidification – Solid State Electrode, Canister
Flush Cycle Automatic Automatic Automatic Automatic Automatic
kg/hr (lb/hr) 8.0 (17.6) 8.0 (17.6) 15.0 (33.1) 15.0 (33.1) 15.0 (33.1)
Electric Reheat – Equally Loaded Three (3) phase
Capacity - kW (BTU/hr) - Includes Motor Heat
400 V 12 (40982.4) 18 (61473.6) 18 (61473.6) 27 (92210.4) 27 (92210.4)
Number of Stages23333
Downflow Filters - mm Quantities
1050 x 453 x 47 G4 22111
1050 x 398 x 47 G4 N/A 1345
Upflow Filters - mm Quantities
700 x 340 x 47 G4 1 1 N/A 1 1
700 x 332 x 47 G4 N/A 1 N/A N/A 1
700 x 502 x 47 G4 11111
700 x 508 x 47 G4 N/A N/A 1 2 2
700 x 508 x 47 G4 N/A N/A 1 N/A N/A
Physical Data
Weight - kg (lb) 372 (820) 480 (1056) 600 (1322) 740 (1631) 884 (1949)
Height - mm (in) 1980 (77.95) 1980 (77.95) 1980 (77.95) 1980 (77.95) 1980 (77.95)
Width - mm (in) 1000 (39.37) 1400 (55.11) 1750 (68.90) 2150 (84.65) 2550 (100.39)
Depth - mm (in) 890 (35) 890 (35) 890 (35) 890 (35) 890 (35)