APC ACPCW40-150 Air Conditioner User Manual


 
15InRoom Precision AC Tech Data Manual
InRoom Condensers - 50 Hz
* Condenser connections may not represent actual line sizing.
InRoom Remote Outdoor Condenser Data, 97°F ambient, 120°F condensation - R407C
InRoom Cabinet Size 1 2 3 4 5
Condenser Model (Qty) ACCD76002 ACCD76003 ACCD76002 (2) ACCD76003 (2) ACCD76011(2)
Voltage 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Number of Fans 2 2 3 3 3
Airflow m
3
/h (cfm) 13600 (8024) 13000 (7670) 13600 (8024) each 13000 (7670) each 16800 (9912) each
Motor kW (HP) -
2 x 0.69
(2 x 0.92)
2 x 0.69
(2 x 0.92)
2 x 0.69
(2 x 0.92)
2 x 0.69
(2 x 0.92)
3 x 0.69
(3 x 0.92)
Refrigerant Connections*
Hot Gas Line - in 7/8 OD 7/8 OD 7/8 OD 1 3/8 OD 7/8 OD
Liquid Line - in 7/8 OD 7/8 OD 7/8 OD 7/8 OD 7/8 OD
Weight - kg (lb) 72 (158) 81 (178) 2 x 72 (2 x 158) 2 x 81 (2 x 178) 2 x 144 (2 x 317)
InRoom Remote Outdoor Condenser Data, 115°F ambient, 131°F condensation - R407C
Condenser Model (Qty) ACCD76003 ACCD76011 ACCD76001 (2) ACCD76011 (2) ACCD76019(2)
Voltage 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Number of Fans 2 2 3 3 3
Airflow m
3
/h (cfm) 13000 (7670) 16800 (9912) 13000 (7670) each 16800 (9912) each 24000 (14160) each
Motor kW (HP) -
2 x 0.69
(2 x 0.92)
3 x 0.69
(3 x 0.92)
2 x 0.69
(2 x 0.92)
2 x 0.69
(2 x 0.92)
3 x 0.62
(3 x 0.83)
Refrigerant Connections*
Hot Gas Line - in 7/8 OD 7/8 OD 7/8 OD 7/8 OD 1 3/8 OD
Liquid Line - in 7/8 OD 7/8 OD 7/8 OD 7/8 OD 7/8 OD
Weight - kg (lb) 81 (178) 144 (317) 2 x 81 (2 x 178) 2 x 144 (2 x 317) 2 x 200 (2 x 440)
na2856a
50 Hz