APC ACPCW40-150 Air Conditioner User Manual


 
InRoom Precision AC Tech Data Manual26
Air Cooled (DX) Continued PA211
Cabinet Size 1
PA311
Cabinet Size 2
PA452
Cabinet Size 3
PA612
Cabinet Size 4
PA862
Cabinet Size 5
Fan Information
Number of Fans 1 1 2 2 3
Air Flow - M³/hr (CFM) 7493 (4,410) 10007 (5,890) 14000 (8,240) 20116 (11,890) 24007 (14,130)
External Static Pressure - Pa (in WC) 50 (0.2) 50 (0.2) 50 (0.2) 50 (0.2) 50 (0.2)
Sound Power Level - dBA 75.40 79.30 77.40 83.20 81.50
Total Fan Power Consumption - kW (hp) 1.7 (2.3) 2.1 (2.8) 3.1 (4.2) 6.1 (8.2) 6.2 (8.3)
Connection Sizes
Number of DX Circuits 1 1 2 2 2
Liquid Line O.D. - mm (in) 12 (1/2) 16 (5/8) 16 (5/8) 16 (5/8) 16 (5/8)
Discharge Line O.D. - mm (in) 16 (5/8) 22 (7/8) 22 (7/8) 22 (5/8) 22 (5/8)
Humidifier Supply Line - mm (in) 6 (1/4) 6 (1/4) 6 (1/4) 6 (1/4) 6 (1/4)
Condensate Drain Line - mm OD (in ID) 21 (3/4) 21 (3/4) 21 (3/4) 21 (3/4) 21 (3/4)
Humidification – Solid State Electrode, Canister
Flush Cycle Automatic Automatic Automatic Automatic Automatic
kg/hr (lb/hr) 8.0 (17.6) 8.0 (17.6) 15.0 (33.1) 15.0 (33.1) 15.0 (33.1)
Electric Reheat – Equally Loaded Three (3) phase
Capacity - kW (BTU/hr) - Includes Motor Heat
460 V 12.0 (40982.4) 18 (61473.6) 18 (61473.6) 27 (92210.4) 27 (92210.4)
230 V 9.0 (30736.8) 18 (61473.6) 18 (61473.6) 27 (92210.4) 27 (92210.4)
Number of Stages 2 3 3 3 3
Downflow Filters - mm Quantities
1050 x 453 x 47 G4 2 2 1 1 1
1050 x 398 x 47 G4 N/A 1 3 4 5
Upflow Filters - mm Quantities
700 x 340 x 47 G4 1 1 N/A 1 1
700 x 332 x 47 G4 N/A 1 N/A N/A 1
700 x 502 x 47 G4 1 1 1 1 1
700 x 508 x 47 G4 N/A N/A 1 2 2
700 x 508 x 47 G4 N/A N/A 1 N/A N/A
Physical Data
Weight - kg (lb) 353 (778) 453 (999) 556 (1226) 680 (1499) 807 (1779)
Height - mm (in) 1980 (77.95) 1980 (77.95) 1980 (77.95) 1980 (77.95) 1980 (77.95)
Width - mm (in) 1000 (39.37) 1400 (55.11) 1750 (68.90) 2150 (84.65) 2550 (100.39)
Depth - mm (in) 890 (35) 890 (35) 890 (35) 890 (35) 890 (35)